VT500 Temperature sensor

 

Online up-to-date documentation page: https://vutlan.atlassian.net/wiki/spaces/DEN/pages/1834713171/VT500+Temperature+sensor

Product page: https://vutlan.com/digital-output/14-vt500-temperature-sensor.html

Keywords: temperature, temperature sensor, temperature meter, temperature probe, detect temperature, measure temperature, monitor temperature, temperature monitoring, temperature alert, temperature alarm, temperature notification, analog temperature, temperature trigger, monitor heat, dew point,

Function and purpose

The sensor is needed for the measurement of temperature indoors.

"VT500 / Temperature sensor" is an analog plug-and-play temperature sensor for indoor use only. Can be connected to any of the analog ports (A1...A8) of Vutlan monitoring systems.

The accuracy of the sensor is ± 0.15 °C at room temperature.  The maximum distance from the monitoring unit (or sensor extension unit) is 100 meters.

The maximum amount of sensors and maximum length can be extended using the "VT408 / Sensor extension unit".

 

The sensor can not be used on its own. It must be used together with Vutlan monitoring systems.

Technical specifications

Parameter

Description

Parameter

Description

Type:

Analog sensor

Measures:

Temperature

Product dimensions:

(Length, Width, Height) 60×18×18 mm

Cable length:

RJ11 6P4C 2m telephone cable included

Power Consumption:

60 mW

Operating temperature:

Optimal range: -10° C to +80° C

Operating humidity:

0 to 95 % (non condensing)

Mounting possibilities:

Indoor
Rack mountable
Wall mount

Max. distance from the unit:

100 m

Accuracy:

± 0.15 °C at room temperature

Daisy chain:

No

Manufactured in (country):

Manufactured in Slovak Republic, E.U.

HS Code:

9025 11 800

EAN code:

8588009886112


Package includes

Drawings

 

Connecting the sensor

The sensor uses a standard Vutlan analog RJS5 RJ11 sensor cable for connecting to the monitoring unit.

Analog sensor connection

Installation using a sticker and a bracket

Option 1.

There's a round bump at the bottom of the plastic enclosure of the sensor. It is used for fastening when the sensor is mounted on walls using a screw. In the current example, it is not needed. If you are planning to mount a device differently, do not follow this step.

Cut the round bump using a knife so that the bottom of the plastic enclosure will be flat.


Option 2.

a) Stick the mounting sensor to the surface using the sticker.

or

b) Stick a sensor to the surface using a screw.

 

Option 3.

Mount the sensor to the surface using a mounting bracket. The mounting bracket and the sensor can be either attached by the stickers or together with screws and nuts.

Sensor configuration




Copyright:

Vutlan s.r.o. (LLC)

Remote Infrastructure Monitoring and Control

43 ul.Svornosti, 821 06 Bratislava,