VT560 / Smoke detector
Product page: https://vutlan.com/analog-sensors/20-vt560-smoke.html
Datasheet page: https://vutlan.atlassian.net/l/cp/Rebjo6pX
Functional description & components
Function
At installation indoors, inside the rack, etc., the sensor monitors the occurrence of smoke inside the building. It is a daisy chain sensor, max. distance from the monitoring unit is 150 meters.
The maximum amount of sensors and maximum length can be extended using the "VT408 / Sensor extension unit".
Components
The smoke sensor consists of a compact plastic housing with ventilation holes.
The sensor can not be used on its own. It must be used together with Vutlan monitoring systems.
Technical specifications
Feature | Description |
---|---|
Type | Analog |
Dimensions | Ø100×45 mm |
Sensor weight | 150 g |
Packaging weight | 290 g |
Inputs | x2 ports RJ12 |
Operating temperature | Optimal: -10 °C to +55° C Extended: -10 °C to +80° C |
Operating humidity | 5% to 95% (Non-Condensing) |
Average lifespan | >=10 years |
Storage temperature | -10 °C to +55° C |
Storage humidity | 5% to 95% (Non-Condensing) |
Power consumption | 100 mW |
Status Indicators | Red LED |
Max. distance m | 150 m |
HS Code | 8531 10 950 |
Components | Manufactured in E.U. |
Daisy chain | Yes, sensors can be connected in a chain. The system will show all daisy chain sensors in one chain as one sensor. |
Mounting | On the сeiling |
Drawing
|
Package content
Safety instructions
Please observe the valid regulations for installation in the country in which the smoke alarm is installed and operated and the national regulations for accident prevention. Please also observe any internal company regulations, such as work, operating, and safety regulations.
The technical specifications and limit values stated must not be exceeded under any circumstances. In particular, this applies to the specified ambient temperature range and IP protection category.
If a higher IP protection category is required for a special application, the smoke alarm must be installed in an appropriate housing or an appropriate enclosure with the required IP protection category.
Siting location requirements
To ensure the proper functioning of the unit, the conditions for the installation site of the unit specified in section “Technical specifications” must be observed.
Electromagnetic interference
Interfering electrical installations (high frequency) should be avoided.
Installation procedure
Notes on assembly
It is vital to ensure that the smoke alarm is always assembled with the sensor head pointing downwards. In any other position, there is no guarantee that smoke will be detected.
The smoke alarm must also be positioned so that it is ventilated with an adequate amount of air and the ventilation slots are not covered.
Installation with the mounting plate provided
The smoke alarm is installed using the mounting plate provided.
Uncover the smoke detector head from the base.
Attach the smoke sensor base to the mounting plate using the M4 x 10 screws provided.
Replace the sensor head onto the base and secure it by twisting it until it locks home.
Secure the mounting plate to the enclosure frame using the 4.8 x 19 screws.
Remove the red protective cap!
Connecting the smoke sensor
Connect one end of the RJ11 / RJ12 cable to the monitoring unit and the other end to any of the two inputs of the smoke sensor. It is possible to connect up to 10 sensors to one analog port. To do so connect the new RJ11 cable to a free input of the already connected smoke sensor and the other end to the next smoke sensor in a chain. See the picture below. RJ11 or RJ12 cable pinouts can be found in the picture below. After the system will start and sense the smoke detector, the LED on the smoke detector will blink dimly once a second.
Testing the smoke sensors
During system operation, take a needle or paper clip and insert it into the hole on the cover of the sensor, try to move it there until the blinking dimly LED will flash brightly. That means that sensor is in a good state. After inspection, return the sensor /s to a normal state. To do this, either disconnect them from the system, or in a system interface, go to the smoke sensors tab, and restart them.
Connecting analog sensors
Article link: https://vutlan.atlassian.net/wiki/spaces/DEN/pages/1016274
Analog sensor configuration
Article link: https://vutlan.atlassian.net/wiki/spaces/DEN/pages/1016314
Copyright:
Vutlan s.r.o. (LLC)
Remote Infrastructure Monitoring and Control
43 ul.Svornosti, 821 06 Bratislava,
Slovak Republic