VT500 / Temperature sensor (v1) (legacy)
Documentation page: https://vutlan.atlassian.net/wiki/spaces/DEN/pages/1834713171/VT500+Temperature+sensor+v2
Product page: https://vutlan.com/digital-output/14-vt500-temperature-sensor.html
Function and purpose
The sensor is needed for the measurement of temperature indoors.
"VT500 / Temperature sensor" is an analog plug&play temperature sensor for indoor use only. Can be connected to any of the analog ports (A1...A8) of Vutlan monitoring systems.
The accuracy of the sensor is ± 0.15 °C at room temperature. The maximum distance from the monitoring unit (or sensor extension unit) is 100 meters.
The maximum amount of sensors and maximum length can be extended using the "VT408 / Sensor extension unit".
The sensor can not be used on its own. It must be used together with Vutlan monitoring systems.
Technical specifications
Feature | Description |
---|---|
Type | Analog sensor |
Usage | Temperature measurement |
Product dimensions | (Length, Width, Height) 60×18×18 mm |
Packing weight | 70 g |
Packing size | (Length, Width, Height) 45x45x120 mm |
Cable length | 2m (the custom length of the cable is possible) |
Power Consumption | 60 mW |
Operating temperature | Optimal temperature range: -10° C to +80° C Extended temperature range: -40° С to +100° C |
Operating humidity | 0 to 95 % |
Storage temperature | -40° С to +100° C |
Storage humidity | 0 to 95 % |
Mounting possibilities | Desktop, Indoor, Rack-mountable, Wall mount |
Max. distance from the unit | 100 m |
Manufactured in (country) | Manufactured in Slovak Republic, E.U. |
HS Code | 9025 11 800 |
Accuracy | ± 0.15 °C at room temperature |
Daisy chain | Not possible |
Inputs terminals | RJ-11 / 6P4C |
Package includes
Drawings
Connecting the sensor
The sensor uses a standard Vutlan analog RJS5 RJ11 sensor cable for connecting to the monitoring unit.
Analog sensor connection
Installation using a sticker and a bracket
Option 1.
There's a round bump at the bottom of the plastic enclosure of the sensor. It is used for fastening when the sensor is mounted on walls using a screw. In the current example, it is not needed. If you are planning to mount a device differently, do not follow this step.
Cut the round bump using a knife so that the bottom of the plastic enclosure will be flat.
Option 2.
a) Stick the mounting sensor to the surface using the sticker.
or
b) Stick a sensor to the surface using a screw.
Option 3.
Mount the sensor to the surface using a mounting bracket. The mounting bracket and the sensor can be either attached by the stickers or together with screws and nuts.
Sensor configuration
Copyright:
Vutlan s.r.o. (LLC)
Remote Infrastructure Monitoring and Control
43 ul.Svornosti, 821 06 Bratislava,
Slovak Republic
www.vutlan.com