VT420 Converter 4-20mA
- 1 Physical description
- 2 Function and purpose
- 3 Use cases
- 4 Specifications
- 5 Package includes
- 6 How do I know that my sensor can be used together with VT420 / 4-20mA converter?
- 7 Installation instructions (hardware)
- 8 Connecting the sensor to the Vutlan monitoring system
- 9 Sensor settings
- 10 Usage example 1:
- 11 Connecting analog sensors
- 12 Configuring sensors
Product page: https://vutlan.com/4-20ma-sensors/13-vt420-converter-4-20ma.html
Datasheet page: https://vutlan.atlassian.net/wiki/spaces/DEN/pages/125272069/VT420+Converter+4-20mA
Physical description
Side showing output (RJ11 / RJ12) : | Side showing input (terminal plug 2 pins 5mm): |
|---|---|
Function and purpose
The converter of direct current 4-20mA is used for measurement of constant current on 4-20mA from different 3rd party sensors and converting data into the format of the Vutlan monitoring system. The system interface allows you to assign the sensor and introduce the function data conversion.
The sensor is an analog plug-and-play sensor. It can be connected to any analog port of any Vutlan monitoring system or an analog port of the VT408 / Analog extension unit.
The maximum amount of VT420 sensors connected to the Vutlan monitoring system and the maximum cable length can be extended using the VT408 / Sensor extension unit.
Use cases
Industrial Automation: The VT420 is ideal for monitoring processes where current sensors are employed, such as in automated production lines or machinery.
Environmental Monitoring: It can be used in environmental systems that rely on current-based sensors for tracking variables like temperature, humidity, or pressure.
Specifications
Function & purpose | Description |
|---|---|
Device type: | Analog sensor and 4-20mA converter |
Used for: | 4-20mA current loop converter, sensor, adapter |
Measured current: | 4-20 mA |
Accuracy: | 2% |
|
|
Communications | Description |
Output: | x1 RJ-12 / RJ-11 6p4c |
Input: | Terminal plug 2 pins, pitch 5mm |
Maximum distance: | 50 meters from the monitoring unit or VT408 extension unit |
|
|
Envrironmental | Description |
Operating temperature: | Optimal range: -10° C to +80° C |
Operating humidity: | Min. 5% - Max. 95% (Non-Condensing) |
|
|
Mechanical | Description |
Size: | L60×H18×D18 mm |
Weight: | 60 g |
Mounting: | Wall mount, rack mount |
Isolation: | Galvanic isolation of 1 kV between I/O is used in a receiver. |
Power Consumption: | 100 mW |
|
|
General | Description |
Origin: | Made in EU |
HS Code: | 9030 33 100 |
GTIN: | 8588009886242 |
Warranty: | 90 days |
Package includes