VT510 Humidity sensor
Product page: https://vutlan.com/analog-sensors/16-vt510-humidity.html
Datasheet page: https://vutlan.atlassian.net/l/cp/121FNA2f
|
Function and purpose
The VT510 / Relative Humidity Sensor is designed for precise measuring indoor relative humidity levels ranging from 10% to 95%. It’s an analog plug-and-play sensor that seamlessly integrates with Vutlan monitoring units.
This sensor can be connected to any analog port (A1...A8) of the Vutlan monitoring system, providing real-time humidity data. The maximum number of sensors and the distance from the monitoring unit can be extended using the "VT408 / Sensor extension unit", offering greater flexibility for larger installations.
Use cases
These examples show the sensor’s versatility in various fields where monitoring and maintaining optimal humidity is crucial.
Data Centers and Server Rooms: Used to monitor humidity levels, preventing moisture buildup that could damage sensitive electronic equipment and lead to downtime or hardware failure.
Industrial Automation: Helps maintain optimal environmental conditions in factories, warehouses, and production facilities where humidity control is critical for processes, equipment longevity, or product quality.
Clean Rooms: In pharmaceutical or electronics manufacturing, maintaining precise humidity levels is essential to avoid contamination or static electricity that could impact product quality.
HVAC Systems: Provides real-time data for climate control systems, enabling efficient regulation of humidity in buildings and ensuring a comfortable indoor environment.
Laboratories: Ensures that controlled environments like research labs maintain proper humidity levels for experiments, equipment, and sample storage.
Greenhouses and Indoor Farming: Vital for controlling the humidity necessary for plant growth and preventing mold or fungal growth.
Technical specifications
VT510 | ||
---|---|---|
1 | Product dimensions | (Length, Width, Height) 60×18×18 mm |
2 | Measures | Relative humidity |
3 | Power Consumption | 60 mW |
4 | Operating temperature | Temperature: Min. -10° C - Max.+80° C |
5 | Operating humidity | 10-95% indoors |
6 | Mounting possibilities | Desktop and Wall mount |
7 | Max. distance from the unit | 50 m |
8 | Manufactured in (country) | Manufactured in Slovak Republic, E.U. |
9 | Accuracy | 3% RH |
10 | Inputs terminals | RJ-12 / RJ-11 |
11 | HS Code | 9025 11 800 |
12 | GTIN | 8588009886136 |
Drawings
Package includes
Connecting vibration sensor
The sensor uses a standard Vutlan analog sensor cable for connecting to the monitoring unit. You can find further instructions at Analog sensors connection
Installation using a sticker and a bracket
Option 1.
There's a round bump at the bottom of the plastic enclosure of the sensor. It is used for fastening when the sensor is mounted on walls using a screw. In the current example, it is not needed. If you are planning to mount a device differently, do not follow this step.
Cut the round bump using a knife so that the bottom of the plastic enclosure will be flat.
Option 2.
a) Stick the mounting sensor to the surface using the sticker.
or
b) Stick a sensor to the surface using a screw.
Option 3.
Mount the sensor to the surface using a mounting bracket. The mounting bracket and the sensor can be either attached by the stickers or together with screws and nuts.
Cable pinouts
The sensor uses a standard Vutlan analog sensor cable for connecting to the monitoring unit. You can find further instructions in our online documentation: Analog sensors connection
Copyright:
Vutlan s.r.o. (LLC)
Remote Infrastructure Monitoring and Control
43 ul.Svornosti, 821 06 Bratislava,
Slovak Republic