Function and purpose

For the installation at the bottom of IT racks and cabinets; at the bottom of raised floors; at the bottom of trays and under equipment that can potentially leak. When water is in contact with both metal cores, the sensor indicates the emergence of moisture.
Attention! Metal cores are detectors of water, mount strictly downwards as close as possible to a floor.

Technical specifications

CommunicationsDescription
Sensor type:Analog sensor
Outputs:x1 RJ11 6P4C port
Daisy chain?No
Max. distance from the monitoring unit:100 m
Environmental
Operating temperature:Min. -10 °C - Max.80 °C
Operating humidity:5 to 95% (Non-Condensing)
Power requirements
Power consumption60mW
Mechanics
Dimensions:60×18×18 mm
Mounting:Mounting bracket included. Installed at the bottom of racks or floors or trays.
Packaging weight:125 g
Cable length:3m
General
Manufactured in:Slovak Republic, European Union
Manufactured by:Vutlan s.r.o.
HS Code:9025 80 400
Warranty:90 days


Package includes

Unable to render {include} The included page could not be found.

Drawings

Connecting the leak sensor

The sensor uses a standard Vutlan analog sensor cable for connecting to the monitoring unit. You can find further instructions at: Analog sensors connection

Installation using a sticker and a bracket

1) There's a round bump at the bottom of the plastic enclosure of the sensor. It is used for fastening when the sensor is mounted together with the on walls using a screw. In the current example, it is not needed. If you are planning to mount a device differently, do not follow this step.

Cut the round bump using a knife so that the bottom of a plastic enclosure will be flat.


2) a) Stick the mounting bracket to the bottom surface.

    b) Stick a sensor to the mounting bracket following the rule from the next paragraph.


3) If  Depending on the surface where the sensor will be installed follow either A or B. If the surface is conductive, then the electric loop between left and right metal bars sticking out the sensor will be closed, which means there's water that connects two bars.

A) If the surface is not conducive. Then mount the sensor metal bars as close to the surface as possible.

B) If the surface is conductive. Then mount the sensor metal bars a bit further from the surface but not too far, so that the detection of water would be possible.


4) The sensor is mounted.

Installation examples

Please find installation examples in our article "Water leakage detection using cable sensor and spot sensor" https://vutlan.com/blog/post/leakage-detection.html.

Connecting analog sensors

The sensor uses a standard Vutlan analog sensor cable for connecting to the monitoring unit.

This section includes child pages:

Connecting analog sensors

Connect the analog sensor by a supplied RJ-11 (6P4C) cable to any analog port "A1 .. A8" or "Sensor" port. The determination of the sensor type and connection will occur automatically.

Vutlan analog sensor connection (Analog ports).jpg

If strong electromagnetic interference is present, we recommend using a 3-pair cable CAN FTP for sensor connection!

6P4C RJ11 cable wiring/pinouts

RJ11 RJ12 (6p4c) pinouts cable.jpg

1- Yellow, 2- Green, 3- Red, 4 - Black

Colors are true for this telephone cable. Both ends match the colors and pinouts (identical).

Please refer to the RJ connectors comparison table:

Daisy chain connection

Some of the analog sensors can be connected to a daisy chain. Please refer to the article "Chain Connection of analog sensors".

Maximum cable length test

ok = tested

x = failed

Model

50m

100m

120m

150m

200m

VT407

AC current converter

ok

recommended

  ok




VT410

DC voltage monitor

ok





VT420

Converter 4-20mA

ok

recommended

ok




VT500

Temperature sensor

ok

ok




VT501

Outdoor temperature sensor

ok

ok




VT510

Humidity sensor

ok

x




VT530

Access sensor


ok




VT540

Vibration sensor


ok




VT550

Wind velocity meter

ok

x




VT560

Smoke detector


ok




VT570

PIR sensor


ok




VT590

Spot water detector


ok




VT591

Water leak sensor


ok




Extending the number of analog sensors

Using CAN extension "VT408 / Sensor extension unit" it is possible to increase the number of analog sensors connected to the monitoring unit up to 80 sensors.

Analog sensors using CAN bus (Vutlan).jpg

Additional articles of interest

Sensor configuration

Adding logic schemes

Configure analog sensors

Settings tab

To configure a sensor, go to "Main menu" >> "System tree" and click on the sensor element in the tree. A modal window with sensor properties will pop up. Change the needed settings and click "OK" or "Apply" at the bottom of the "Properties" window.

All sensors include:

1

Name

The name is given by the system automatically. You can change it to anything you want.

3

ID

System ID of the element.

4

Type

Examples: temperature, humidity, vibration.

5

Class

Examples: analog, CAN, switch, discrete.

6

Hardware port

The external port number on the device panel to which the sensor is connected (if the sensor is external).

All sensors have threshold controls:

In the picture above, the "Current value" equals 41.0 and is represented by the small triangle. Currently, the triangle is green because it is situated in the "Normal" range. Hence the sensor says that the "Current state" is "Normal". This value is used by the system's "Logic schemes" menu to notify the administrator or take action.

Hysteresis

Sensors have the option of setting the hysteresis state. Hysteresis can be a time, a value or it can be disabled.

If the hysteresis is set in time, the sensor will transmit to a new state with a delay of the specified number of seconds in the corresponding field. The time counting will begin from the moment when the measured value of the sensor has left the current range.
Each state has its own field. Which determines the time that the sensor value must continuously hold for the state to change to the specified.

If you set the hysteresis by value, the sensor transition to a new state will occur when the measured value of the sensor exits beyond the current range, adjusted for the specified hysteresis value.

You can calibrate the sensors. Use K and B coefficients. After the calibration, please, save the values in flash memory.

To save sensor properties in the device's flash memory press "  "  then "OK" to confirm. 

Example: Why do we need to use Hysteresis

Let’s say that we have a temperature sensor. Let’s say that we have set up threshold values.

We have set the value 25.5 °C to be a threshold value between Normal/Alarm states.

If the temperature drops just below 25.5 °C You will have a “Normal” state.

If the temperature goes just above 25.5 °C You will have a “Warning” state.

Sometimes the temperature may stay at 25.5 °C and jump up and down by 0.1-0.3 °C. In this case, You will get too many notifications that the sensor is showing a Warning or Normal state.

In this case, we need to use a Hysteresis.

If the type “time” is chosen, the system will wait for a specified time before the State of the sensor is declared.

If type “value” is used, unless the temperature drops by a larger amount than specified, the sensor state will not be declared.

Tuning the sensor value

Sensor readings can be tunned by a linear formula "y = k * x - b"

Example VT407 + HAT-100Q1 / AC current converter:

Metered current for HAT: from 0 to 100A (This means that the range equals 100, k = 100)

The output of VT407 is 0-5V (That means that the range is equal to 5)

"b" = the value that the sensor shows in WebUI when there's no current. Let's say that b = + 0.021

You should use the following formula for HAT: 100/5*(x-y)

The expression formula would be 20*(x-0.021)

Point is used as a decimal separator (3.14)

Charts tab

The charts tab shows the following:

Display chart for

  • last 100 seconds

  • last 100 minutes

  • last 100 hours

  • last 100 days


Refresh data

Start

Poll a sensor

Reset all charts

Reset all

Clears all saved data for the sensor.

Export data

XML or CSV

Exporting data through WebUI does not work for more than a couple of days and is very rough. If you need detailed log data, use the logging of sensor values to the media.
Read more at: System Log, Sensors dump files.

Note: Make sure no endpoint security services used in the network are not blocking the download of XML and CSV files.

Reset smoke sensors

If analog sensors like VT560 / Smoke detector/ sensor detects smoke or fire, it will go into Alarm mode. Alarm mode can only be switched off manually using the Reset smoke detectors panel or using the onboard sensor Analog sensor power reset is found in the System tree >> Onboard.

API: managing system elements by 3rd party Software

Vutlan has an open API. Read more at:

https://vutlan.atlassian.net/wiki/spaces/API/pages/335740995/Managing+system+elements





Copyright:

Vutlan s.r.o. (LLC)

Remote Infrastructure Monitoring and Control

43 ul.Svornosti, 821 06 Bratislava,

Slovak Republic

www.vutlan.com

  • No labels