VT594 / BMS leak water sensor

keywords: BMS leak detection, Building Management System leak monitoring,

Function and purpose

Product page: 

Datasheet page: https://vutlan.atlassian.net/wiki/spaces/DEN/pages/3036315649/

VT594 BMS leak water sensor (back).png

 

VT594 BMS leak water sensor (front).png

The sensor must be used together with

WLC / Water leak cable

(ordered separately)

WLC / Water leak cable

(ordered separately)

"WLC / Water leak cable" is ordered separately!  When water is in contact with the detection cable sensor indicates the emergence of moisture. The whole area can be effectively monitored by placing the cable near or along with possible flood sources.

Order options

Model number

Power supply voltage

Model number

Power supply voltage

VT594-12

12V DC

VT594-24

24V DC

Dimensions

Usage examples

 

 

Technical specifications

VT594 / BMS water leak sensor specifications
VT594 / BMS water leak sensor specifications

Dimensions

60×18×18 mm

Weight

60 g

Input

2 wire (WLC cable)

Output

RJ11 / RJ12 (6p4c)

Operating temperature

-10 °C to +80 °C

Operating humidity

5% to 95% (Non-Condensing)

Mounting

Mounting bracket included.

Power consumption

60mW

Max. distance m

100 m

Power supply voltage

optional order: 12V DC or 24V DC

HS Code

9025 80 400

Components

Manufactured in E.U.

Special features

Response time: 15 sec., Recovery time: Depends on how fast the sensor dries out

WLC / Water leak cable specifications

WLC / Water leak cable specifications

Description

WLC can work in high humidity, pollution, and hazardous waste

Detectable liquids

Clean, polluted & distilled water; acids; alkalis; alcohols, and other electrically conductive liquid

Diameter

6.5 mm in diameter

Lengths

Order options include 10m, 15m, 25m, 50m, or custom length.

Weight

36 g/m

Operating humidity

0% - 95 %

Max. storage temperature

75°C

Max. cable length

100 m

Inputs

x2 wires

Package content

Connecting WLC / Water leak cable

Model VT594-12 (Power supply voltage is 12V DC)

 

Model VT594-12 (Power supply voltage is 24V DC)

 

Do not do illustration

Description

Do not do illustration

Description

The cable can not touch itself. It needs to be straightened.

 

Do not twist or press down the cable too much. This may lead to deformation. The cable has two sensing wires, these wires can not touch each other.

 

Do not put the cable on a conductive surface.

 

  1. Connect the "VT594 / Water leak sensor" to any BMS unit dry contact and 12-24V input, Gnd.

  2. Connect the "Terminal cable" to the VT594 sensor.

  3. Connect "WLC / Water detection cable" to "Terminal cable".

  4. Connect any additional "WLC / Water detection cables" to each other as shown in the picture above to make a chain connection.

  5. Wire the WLC rope around or under potentially leaking objects around the perimeter or under the raised floors.

  6. Put a protective cap on the connector of the last WLC cable in a chain.

  7. The sensor is ready to use.

How to test the sensor & sensor cable

  1. Connect the WLC cable to VT594 by terminal cable. Connect VT594 to dry contact, voltage and ground points of the BMS system. Make sure that the WLC cable is straight or not contacting itself, or any conducting material. The sensor should appear in the BMS system as “Normal” (if the behavior is set to “Normal”), which means that there’s no presence of liquid (the two yellow wires along the WLC cable are not cables shorted).

  2. Take a rag and wet it a little. Touch the rag to both yellow wires on the WLC cable. This should shorten the contact. The VT594 sensor should change the state to “Alarm”.

  3. Dry the cable carefully with a dry cloth.

Cable layouts

 

Cover the whole area

Comprehensive protection for critical areas

Cover the edge area

Prevent leaks from immersing in or spreading out

Covering air-conditioned areas

Key protection against major leakage sources such as alr conditioners

Schematics / Sensitivity adjustment

You can change the a resistor using the following schemes.

For example, if your room has very high humidity and the cable is in an alarm state without the spilled liquid being present, you can change R10 to 270k. This should lower the sensitivity level.

Model VT594-12 (power supply voltage 12VDC)

 

Model VT594-24 (power supply voltage 24VDC)

Troubleshooting

The following table describes potential problems and their possible causes. It also describes checks you can perform or possible solutions for each. After referring to this table, if you cannot resolve the problem, contact your local Vutlan sales representative for assistance.

Potential Problem

Possible Cause

Possible Solution

Potential Problem

Possible Cause

Possible Solution

The data being displayed is inaccurate or not what you expect.

Incorrect setup values.

Check that You use the correct f(x) formula

Incorrect voltage inputs.

Check power meter voltage input terminals to verify that adequate voltage is present

The power meter is wired improperly.

Check that all wires are connected correctly and that they are energized. See “Wiring Diagrams” of the device.

The sensor does not appear in the Vutlan monitoring interface

Communication lines are improperly connected.

Check the 6P4C RJ11 communication cable.

The communication cable is inserted into the wrong port.

6P4C RJ11 communication cable must be inserted into the analog port of the Vutlan monitoring system.

The sensor is always in alarm state.

The cable touches itself.

The cable can not touch itself. It needs to be straightened. Please check if the cable is bent anywhere.

The cable is twisted or pressed down too much.

Do not twist or press down the cable too much. This may lead to deformation. The cable has two sensing wires, these wires can not touch each other.

The cable is located on a conductive surface.

Do not put the cable on a conductive surface.

The cable is damaged

Check the continuity of the cables with a multimeter. Let’s call each wire A and B:

If the cable is not damaged, you should get the following results

  1. A-A: there’s a continuity. (I think it’s good)

  2. A-B: there’s a continuity. (I think there shouldn’t be any)

  3. B-B: there’s a continuity

 

If the cable is damaged, you will get:

  1. A-B: there’s a continuity. There should not be a continuity. The wires cross each other somewhere.

or

  1. B-B or A-A: no continuity (the wire is damaged).