VT11 / Relay output

Documentation page: https://vutlan.atlassian.net/wiki/spaces/DEN/pages/583237633/VT11+Relay+output

Product page: https://vutlan.com/digital-output/72-vt11-relay-contact-5a.html

Function and purpose

Relay switchable contact. Can be used together with equipment, for example for switching it ON/OFF. For controlling devices that have dry contact input or controlling their power source. Can manage 5A power for magnetic locks, bolt locks, solenoid electromagnets, sirens, light sources, heaters, air conditioners, etc.

Can be connected to any Vutlan unit with 12V relay outputs.

Technical specifications

VT590
VT590

Dimensions

60×18×18 mm

Weight

60 g

Input

wire terminal 3.81mm 2P

Outputs

wire terminal 5.0mm 2P

Operating temperature

Temperature: Min. -50 °C - Max.105 °C

Operating humidity

Humidity : Min. 5% - Max. 95% (Non-Condensing)

Mounting

The mounting bracket, sticker, and screws are included.

Power consumption

12 mW

Max. distance m

200 m

HS Code

9025 11 800

Components

Manufactured in E.U.

Special features

Can be connected to any monitoring system or device with 12V outputs.

Max. switching voltage

250VAC / 30VDC

Max switching current

5A

Max. switching power

1250VA / 150W

Min. contact load

No gold plated: 5VDC 10mA

LED indication

The sensor has a red LED indicator that sticks from the top cover

 

Normal

Reverse

 

Normal

Reverse

contact is closed

Red

-

contact is open

-

Red

Drawings

Connecting switchable contact

Switchable contact can only be connected to 12V 0.25A outputs of the Vutlan monitoring system. The diagram below explains how to connect two VT11 switchable contacts to the monitoring system.

Usage examples with installation diagram

Example 1. Using "VT11 / dry contact output" to control a device with dry contact input.



Example 2. Control siren, light source, heater.



Example 3. Control magnetic lock, electric motor, solenoid electromagnet

 

Cable pinouts

Switchable contact uses a standard two-wire cable for connecting to the monitoring unit.

Packaging includes

Connecting 12V devices to 12V outputs

Configuring 12V relays




Copyright:

Vutlan s.r.o. (LLC)

Remote Infrastructure Monitoring and Control

43 ul.Svornosti, 821 06 Bratislava,

Slovak Republic

www.vutlan.com