VT590 / Spot Water Detector (legacy)
End of Life: 30.09.2023
Documentation page: https://vutlan.atlassian.net/wiki/spaces/DEN/pages/93421575/VT590+Leak+sensor
Product page: https://vutlan.com/analog-sensors/22-vt590-spot-water-detector.html
Function and purpose
For the installation at the bottom of IT racks and cabinets; at the bottom of raised floors; at the bottom of trays and under equipment that can potentially leak. When water is in contact with both metal cores, the sensor indicates the emergence of moisture.
Attention! Metal cores are detectors of water, mount strictly downwards as close as possible to a floor.
Technical specifications
Communications | Description |
---|---|
Sensor type: | Analog sensor |
Outputs: | x1 RJ11 6P4C port |
Daisy chain? | No |
Max. distance from the monitoring unit: | 100 m |
Environmental | |
Operating temperature: | Min. -10 °C - Max.80 °C |
Operating humidity: | 5 to 95% (Non-Condensing) |
Power requirements | |
Power consumption | 60mW |
Mechanics | |
Dimensions: | 60×18×18 mm |
Pin diameter | 4mm ⌀ |
Pin length | From pin top to enclosure: approximately 8.4mm |
Mounting: | Mounting bracket included. Installed at the bottom of racks or floors or trays. |
Packaging weight: | 125 g |
Cable length: | 3m |
General | |
Manufactured in: | Slovak Republic, European Union |
Manufactured by: | Vutlan s.r.o. |
HS Code: | 9025 80 400 |
Warranty: | 90 days |
Package includes
Carton box 131x125x42 (W, L, H)
Package content | Description | |
---|---|---|
1 | x1 pc, Water detector probe with 3m cable | |
2 | Bracket | |
3 | x1 pc, Screw 4,2*16 | |
4 | x2 pcs, Bolts М3.5x10 | |
5 | x2 pcs, М3.5 Nuts | |
6 | x2 pcs M3.5. washers | |
7 | x1 pc, Two sided sticker |
Drawings
Connecting the leak sensor
The sensor uses a standard Vutlan analog sensor cable for connecting to the monitoring unit. You can find further instructions in Analog sensors connection
Installation using a sticker and a bracket
1) There's a round bump at the bottom of the plastic enclosure of the sensor. It is used for fastening when the sensor is mounted on walls using a screw. In the current example, it is not needed. If you are planning to mount a device differently, do not follow this step.
Cut the round bump using a knife so that the bottom of a plastic enclosure will be flat.
2) a) Stick the mounting bracket to the bottom surface.
b) Stick a sensor to the mounting bracket following the rule from the next paragraph.
3) Depending on the surface where the sensor will be installed follow either A or B. If the surface is conductive, then the electric loop between the left and right metal bars sticking out of the sensor will be closed, which means there's water that connects the two bars.
A) If the surface is not conducive. Then mount the sensor metal bars as close to the surface as possible.
B) If the surface is conductive. Then mount the sensor metal bars a bit further from the surface but not too far, so that the detection of water would be possible.
4) The sensor is mounted.
Installation examples
Please find installation examples in our article "Water leakage detection using cable sensor and spot sensor".
Connecting analog sensors
The sensor uses a standard Vutlan analog sensor cable for connecting to the monitoring unit.
Configure analog sensors
API: managing system elements by 3rd party Software
Vutlan has an open API. Read more at:
Analog sensors API: https://vutlan.atlassian.net/wiki/spaces/API/pages/335806556/Analog+sensors