VT540 / Vibration sensor v1 (legacy)
Product page: https://vutlan.com/analog-sensors/19-vt540-vibration.html
Datasheet page: https://vutlan.atlassian.net/l/cp/jzDSR4KK
|
---|
Function and purpose
Detects vibration. For installation on walls, windows, etc., the sensor controls vibration. For example, detects the breaking of the window by an intruder if installed on the window glass.
Technical specifications
Feature | Description |
---|---|
Sensor type | Analog sensor |
Dimensions | 60×18×18 mm |
Weight | 60 g |
Input | RJ-12 / RJ-11 (6p4c) |
Outputs | RJ11 / RJ12 (6p4c) |
Operating temperature | -10 °C to +80 °C |
Operating humidity | 5% to 95% (Non-Condensing) |
Mounting | The mounting bracket, sticker, and screws are included. Installed on the surface where possible vibration is possible. E.g. windows, doors, etc. |
Power consumption | 60mW |
Max. distance m | 150 m |
HS Code | 9025 11 800 |
Components | Manufactured in E.U. |
Daisy chain possible | No |
Package includes
Drawing
Connecting vibration sensor
The sensor uses a standard Vutlan analog RJS5 RJ11 sensor cable for connecting to the monitoring unit.
Installation using a sticker and a bracket
Option 1.
There's a round bump at the bottom of the plastic enclosure of the sensor. It is used for fastening when the sensor is mounted on walls using a screw. In the current example, it is not needed. If you are planning to mount a device differently, do not follow this step.
Cut the round bump using a knife so that the bottom of a plastic enclosure will be flat.
Option 2.
a) Stick the mounting sensor to the surface using the sticker.
or
b) Stick a sensor to the surface using a screw.
Option 3.
Mount the sensor to the surface using a mounting bracket. The mounting bracket and the sensor can be either attached by the stickers or together with screws and nuts.
Analog sensor connection
Configuring the sensitivity of the sensor
The sensor is very sensitive. At times this may prove to be too sensitive. In this case, it is possible to lower the sensor's sensitivity:
1) Unplug the sensor from the cable.
2) Open the sensor cover using a flat screw.
3) Take the two-pin jumper header out. This will lower the sensitivity slightly.
4) Close the cover and plug the sensor back in.
If the sensitivity is still too high, Vutlan can produce a custom vibration sensor will a much lesser sensitivity on demand. In this case, please contact the sales team.
Sensor configuration
Copyright:
Vutlan s.r.o. (LLC)
Remote Infrastructure Monitoring and Control
43 ul.Svornosti, 821 06 Bratislava,
Slovak Republic