Reservation of current settings

Saving the current monitoring settings

Monitoring settings are not saved after a reboot. To save after reboot, you need to make a call:

“savetoflash” - saves current settings to flash memory;

Reservation of settings via HTTP

The current settings are reserved by calling “settings.htm” ("GET" method)

If you call without parameters (“param” field is absent), all settings are backed up.

To selectively reserve settings, you must set the appropriate parameters in the “param” field, using a space as the separator.

 

Table. Parameters of selective reservation

Parameter

Description

Parameter

Description

monitoring

Monitoring: modules, sensors, groups, map, USB web-cam etc

canbus

CAN bus configuration

dbusers

Users DB

dbkeys

Access keys DB

datetime

Date and time configurations

network

Network settings

http

HTTP Server settings

log

Logging settings

radius

Radius settings

snmp

SNMP settings

dyndns

DynDNS

update

Settings of update

backup

Settings of backup

Reservation of settings for external FPP by schedule

  • getftpbackup - get FTP backup settings;

  • setftpbackup - set the parameters of FTP Backup:

    • noreboot - if the key is equal to "1", then the reboot, after the configuration of the settings, will not be performed;

    • address - the address of the FTP server;

    • port - FTP server port;

    • rdir - remote directory on the FTP server;

    • username - FTP server username;

    • password - FTP server user password;

    • interval - backup interval:

      • 'never' - the function is disabled;

      • 'daily' - daily;

      • weekly - weekly;

      • "monthly" - monthly;

    • day - day (week or month) of reservation (for the day of the week (1..7), 1 means Monday));

    • hour - hour of reservation (00..23);