Function and purpose
VT225t Room Monitoring Unit is a low-cost remote environmental monitoring unit that is ideal for small IT rooms, offering comprehensive monitoring and control. It tracks various environmental parameters, including temperature, humidity, voltage, leakage, smoke, and airflow, ensuring optimal conditions for sensitive equipment. The unit also functions as an I/O controller, managing devices such as doors, fans, generators, UPS systems, alarms, and circuit breakers.
Key features include:
Ability to signal alarms, activate sirens, send email notifications, or dispatch SNMP traps.
Support for up to 100 physical sensors and up to 700 elements like notifications, logic circuits, and triggers.
Built-in web interface with virtual sensors, customizable notifications, and control panels.
Compatibility with multiple protocols and services such as HTTP/HTTPS, SNMP (v1, 2c, 3), SMTP, Radius, Syslog, FTP, DHCP, and OpenVPN clients.
This unit provides an affordable solution for ensuring the safety and functionality of IT rooms while maintaining real-time monitoring and control.
Use cases
The VT225t / Remote Monitoring System can be highly effective for small IT rooms in several ways:
Workspace Environmental Monitoring: It monitors indoor temperature, humidity, and air quality to ensure a comfortable and safe environment for employees. This can also help prevent issues with HVAC systems or early detection of fire hazards through smoke and airflow sensors.
Security Control: It can integrate with office access control systems for monitoring doors and windows, ensuring security compliance by triggering alarms in case of unauthorized access or during off-hours.
Utility Management: By monitoring voltage, energy consumption, and other electrical parameters, the system helps optimize energy usage, ensuring cost-efficiency in lighting, server rooms, and other office equipment.
Automated Notifications and Triggers: The system can be programmed to automatically notify maintenance or security personnel through email or SNMP traps in case of an emergency, like a power outage or critical system failure, ensuring prompt responses to minimize downtime.
Smart Office Management: VT225t can integrate with IoT devices, enabling automated control over office lighting, fans, or blinds based on sensor data, which helps in creating energy-efficient smart offices.
The system offers a cost-effective solution to office environments, enhancing security, comfort, and efficiency.
Physical Description
Front panel:
Back panel:
Side panel:
1. "USB" - micro USB-port 2.0 is needed for USB camera recording, USB Flash for system logs, and system restoration. Read instructions in "Connecting USB camera", "USB camera settings. How to save a video", "Saving system logs on USB flash drive", and "USB upgrade or restore of default settings".
2. "Analog sensors: A1..A4" - x4 RJ12 6P4C analog sensor inputs with auto-sensing. Read instructions at "Analog sensors connection", and "Sensor configuration".
3. "SD card" - MicroSD card slot with an ejector. The card is needed for data storage or the "system restore". Read instructions at "Saving system logs to SD card", and "Restore of the appliance (for VT960 series)".
4. "LEDs: R1, R2" - status indicators for two 12V 0.25A outputs on the front panel.
The LED is ON (orange) - the output is ON (the initial state can be configured).
The LED is OFF (orange) - the output is OFF ((the initial state can be configured).
"LED: ACT" - green LED indicates appliance system status,
- operating mode of the device: switches at a frequency of 2 times per second;
- successful completion of the software update process: switches at a frequency of 4 times per second;
"LED: ALARM" - The LED can be programmed from the interface for alarm indication.
"LED: ERR" - red LED indicates error and traffic.
the operating mode of the device: If everything is normal, the LED is extinguished, if not - there's a constant glow;
software update mode: switches at a rate of 2 times per second;
"LED: CAN" - green LED indicates CAN bus status.
The LED blinks slowly - nothing is connected
The LED blinks fast - configuration is in process
The LED glows constantly - connected to CAN devices
5 "RELAYS 12V 0.25A" - 12V 0.25A (for each output) terminals outputs (electronic relay). Pitch 3.81mm, 3P. Each output has an LED indication "E1, E2". Read the instructions at "Connecting 12V devices to 12V outputs".
6. "Restart" - the button restarts the appliance. Hold the button for 2 seconds and then let go, and the system will restart.
7. "Reset settings" - reset settings to default factory settings. Keep pressing the button for more than 5 seconds. The “ERR” LED will start blinking. This indicates that the factory restoration has started. Wait for 20-60 seconds for the system to restart. The “ACT” LED will start blinking once the system has been restarted. The device can be accessed now.
8. "LAN port" - Ethernet 10/100 Base-T port, provides an Ethernet connection. Read more in this section "LAN, GSM, LTE, RADIUS, DNS, SSL, VPN".
"Orange LED" - orange LED for Ethernet port. It shows network traffic.
"Green LED" - green LED for Ethernet port. It shows network traffic. Flashes green when the system starts up. Shows the connection state (constant green light - the connection is established, blinking green - the connection attempt).
9. "CAN" - digital connector RJ12 6P4C for the connection of CAN sensors/extensions/devices on a CAN bus. Modules can be chained together. Has an LED indicator "CAN". Read the instructions in "CAN devises connection", and "Setting up CAN".
10. "DRY CONTACT INPUTS 1...2" - Digital inputs (Type IN). Pitch 3.5mm, 6P. Read the instructions at "Connecting dry contacts", and "Dry contacts settings".
11. "DC 12V POWER"- 12V DC 2A main power input.
12. "Side switch"
“N: Normal mode” - The switch is switched to the left ←. The switch should be always in this position.
“R: Restore of appliance” - The switch is switched to the right →. Used to load the clean system image from an SD card. Read instructions at “Restore of appliance”
Connection overview diagram
Drawing dimensions
Inventory - Package content
Make sure that the contents of the delivery meet the following configuration. Report a missing or damaged component to your supplier. If damage occurred during transportation, contact the appropriate delivery service.
| Package content | Description |
|
|---|---|---|---|
1 |
| Monitoring unit VT225t | 1 pcs |
2 | Wall adapter 12V 1A, 5.5*2.1mm | 1 pcs | |
3 | RJ-45 2m Ethernet cable white | 1 pcs | |
4 | OTG USB-C cable | 1 pcs | |
5 | Terminal 3P, 3.5 mm | 1 pcs | |
6 | Terminal 3P, 3.81 mm | 1 pcs | |
7 | Self-adhesive rubber foot | 4 pcs | |
8 | Short configuration manual |
| |
9 | Warranty card |
|
Technical details
VT335x, VT336x, VT825x, VT855x, VT960x are the monitoring units and can not connect. For scalability please use extension units and embedded boards.
● Built-in □ None ♦ Extension possible ◊ Not extendable
| |||||
|---|---|---|---|---|---|
Device Management: Web, SNMP | Yes | Yes | Yes | Yes | Yes |
| |||||
Interface | |||||
LAN: Ethernet 10/100 Mbit | 100 Mbit | 100 Mbit | 100 Mbit | 100 Mbit | 100 Mbit |
OS: Linux | v.6.2 | v.6.2 | v.6.2 | v.6.2 | v.6.2 |
Memory RAM: | 128 Mb | 128 Mb | 128 Mb | 128 Mb | 128 Mb |
CPU speed: | 1 GHz | 720 MHz | 720 MHz | 720 MHz | 600 MHz |
Total CPU cores: | 2 | 2 | 2 | 2 | 2 |
Clock: Built-in clock | Yes | Yes | Yes | Yes | Yes |
Timer: Built-in watchdog | Yes | Yes | Yes | Yes | Yes |
The maximum amount of sensors: physical sensors, dry contacts, relays | 150 | 130 | 100 | 100 | 100 |
The maximum amount of elements: notifications, triggers, timers, logic, sensors, dry contacts, SNMP Get, SNMP Trap, Dial task, and other elements | 1000 | 1000 | 700 | 700 | 700 |
| |||||
Networking / Protocol support | |||||
LTE Gateway mode: Internet access (routing for internal network) (modem ordered separately) | Yes | Yes | Yes | Yes | - |
LTE Access mode: Internet access over LTE (modem ordered separately) | Yes | Yes | Yes | Yes | - |
Network protocols: DHCP; HTTP; HTTPS; SNMP v1, v2c, v3; SMTP; FTP; Syslog; TLS (v1.0, v1.1, v1.2, v1.3) | Yes | Yes | Yes | Yes | Yes |
Modbus RTU | Using extension VT485m | Using extension VT485m | Using extension VT485m | Using extension VT485m | - |
RS485 / OSDPv2: reader access control | Using extension VT485R | Using extension VT485R | Using extension VT485R | Using extension VT485R | - |
Modbus TCP / IP | Yes | Yes | Yes | Yes | Yes |
Static routing | Yes | Yes | Yes | Yes | Yes |
Dynamic DynDNS | Yes | Yes | Yes | Yes | Yes |
Access via RADIUS server | Yes | Yes | Yes | Yes | Yes |
VPN: secure data communications; secure change of connection between LTE and LAN | Yes | Yes | Yes | Yes | - |
SSL installation | Yes | Yes | Yes | Yes | Yes |
| |||||
Alerts / Notifications | |||||
Alert types: E-mail, FTP log, Syslog, SMTP, SNMP Traps, SMS (Modem is ordered separately), Web-to-SMS, | Yes | Yes | Yes | Yes | Yes |
A maximum number of "mail to" recipients in an E-mail notification: | 20 | 20 | 20 | 20 | 20 |
A maximum number of "SMS to" recipients in an SMS notification: also the maximum amount of phone numbers | 20 | 20 | 20 | 20 | - |
| |||||
Virtual sensors | |||||
Pings: Built-in function for server pinging. Test the reachability of a host in a network. | Yes | Yes | Yes | Yes | Yes |
IP cameras: Connect the IP MJPEG camera with a proxy via the master module. Only view, no record. | 4 | 4 | 4 | 4 | 4 |
Get SNMP: Read data from external equipment via SNMP PDU GET (v1/2c) | Yes | Yes | Yes | Yes | Yes |
User keys: Add users who have access using an RFID reader. | Yes | Yes | Yes | Yes | - |
Logic schemes: Used to specify automatic actions to events that occur in the system. | Yes | Yes | Yes | Yes | Yes |
Timers: Allows you to plan the events in the system. | Yes | Yes | Yes | Yes | Yes |
Triggers: Generate events in the system if logic is triggered. | Yes | Yes | Yes | Yes | Yes |
SNMP traps | Yes | Yes | Yes | Yes | Yes |
Virtual Math element (combine several sensor data and calculate new data) | Yes | Yes | Yes | Yes | Yes |
Logic schemes | Yes | Yes | Yes | Yes | Yes |
Modbus TCP/IP: read/write | Yes | Yes | Yes | Yes | Yes |
| |||||
Power | |||||
Energy efficiency: (EU Energy level) | Grad A | Grad A | Grad A | Grad A | Grad A |
Power input (230V AC): | Two inputs option | Two inputs option | - | - | - |
Power input (24 ÷ 48V DC): | Two inputs option | Two inputs option | Yes | VT335DC | - |
Power input (12V DC): | Input | Input | Two inputs | Input | Input |
Fuse: Fuse at the inlet | 1 A | 1 A | PTC | PTC | PTC |
Min. power consumption: | 1 W | 1 W | 1 W | 1 W | 1 W |
Max. power consumption: | 10 W | 10 W | 10 W | 10 W | 6 W |
The maximum current load on the relay: | 10А | 10А | 250mА | 250mА | 250mА |
Redundant power supply: built-in voltage monitor, voltage range 9-12.6V. | Yes AC/DC; DC/DC | Yes AC/DC; DC/DC | Yes DC/DC | Yes DC 12V | - |
Reduntant battery | Yes | Yes |
|
|
|
| |||||
Outputs | |||||
Relay outputs: latching relays 240V*10A | 2 | 2 |
|
|
|
Relays outputs: 12V 0.25A | 2 | 2 | 2 | 2 | 2 |
Max. dry contact outputs (contact closures/digital outputs) | 8 |
| 5 |
|
|
| |||||
Inputs | |||||
Analog port: 6P6C for connection of an analog sensor. (extendable using CAN bus) | 8 built-in ports, extended using extension unit | 8 built-in ports, extended using extension unit | 4 built-in ports, extended using extension unit | 4 built-in ports, extended using extension unit | 4 built-in ports, extended using extension unit |
CAN port: Max number of sensors Use CAN-12V-1A for connecting more than 12 devices. | x2 port, x32 devices in total (24 max. recommended) | x1 port, max. 32 devices (24 max. recommended) | x1 port, max. 32 devices (24 max. recommended) | x1 port, max. 32 devices (24 max. recommended) | x1 port, max. 10 devices |
Dry contact inputs: (contact closures/digital inputs) | 32 | 16 | 8 | 4 | 2 |
Modbus RTU (RS-485): Max. line length 1000m | Using extension VT485m | Using extension VT485m | Using extension VT485m | Using extension VT485m | - |
OSDP v2 reader extension: | Using extension VT485R | Using extension VT485R | Using extension VT485R | Using extension VT485R | - |
| |||||
Video | |||||
USB cameras | 1 | 1 | 1 | 1 | 1 |
IP cameras | x4 | x4 | x4 | x4 | x4 |
| |||||
Other connectors | |||||
Ethernet port: 10/100Mbit | 1 | 1 | 1 | 1 | 1 |
USB 2.0 Type C | 1 | 1 | 1 | 1 | 1 |
Switch Normal / Recovery: returns the device to factory settings | Yes | Yes | Yes | Yes | Yes |
| |||||
External Memory / Logs | |||||
Micro SD memory card slot (SDXC up to 512 Gb) | Yes | Yes | Yes | Yes | Yes |
SD card formatting function (FAT32) | Yes | Yes | Yes | Yes | Yes |
USB flash drive: logs, sensor readings, item settings, etc. | Yes | Yes | Yes | Yes | Yes |
Send system log to e-mail: Logs, sensor data, elements settings, etc. | Yes | Yes | Yes | Yes | Yes |
Sensor dump files: save the per-second samples of analog and discrete sensors | Yes | Yes | Yes | Yes | Yes |
Yes | Yes | Yes | Yes | Yes | |
Send to FTP server: Logs, sensor data, elements settings, etc. | Yes | Yes | Yes | Yes | Yes |
Maximum amount of log files: up to x3 years | Yes | Yes | Yes | Yes | Yes |
Sample rate/period (logs, graphs) | 1 s | 1 s | 1 s | 1 s | 1 s |
| |||||
Reservation of settings | |||||
“i” series (e.g. VT335i): System settings are compatible | Yes | Yes | Yes | Yes | Yes |
VT335, VT825, VT855 | No | No | No | No | No |
| |||||
Modem (extension ordered separately) | |||||
4G LTE modem: ordered separately. |
| ||||
Modem modes:
| Gateway / Access / SMS | Gateway / Access / SMS | Gateway / Access / SMS
| Gateway / Access / SMS |
|
Modem LED: STATUS | Yes | Yes | Yes | Yes |
|
| |||||
Embedded onboard sensors | |||||
Temperature sensor: +/- 1 °C PCB temperature. | Yes | Yes | Yes | Yes | Yes |
Power supply voltage sensor: Accuracy (1%) | Main & Reserve | Main & Reserve | Main & Reserve | Main & Reserve | Yes |
| |||||
LED indication | |||||
Ethernet LAN: LINK | Yes | Yes | Yes | Yes | Yes |
Ethernet LAN: ACT | Yes | Yes | Yes | Yes | Yes |
CAN bus: STATUS | Yes | Yes | Yes | Yes | Yes |
System: STATUS (ACT) | Yes | Yes | Yes | Yes | Yes |
System: ERROR (ERR) | Yes | Yes | Yes | Yes | Yes |
System: ALARM | Yes | Yes | Yes | Yes | Yes |
12V 0.25A outputs: STATUS (e.g. E1, E2) | 2 | 2 | 2 | 2 | 2 |
MODBUS RTU: STATUS | VT485M | VT485M | VT485M | VT485M |
|
ODSP Reader. | VT485R | VT485R | VT485R | VT485R |
|
NC/NO/COM Relay (e.g. R1, R2) | 2 | 2 |
|
|
|
| |||||
Environmental characteristics | |||||
Operating temperature: -10 to 70 °C | Yes | Yes | Yes | Yes | Yes |
Storage temperature: –25 to 85 °C | Yes | Yes | Yes | Yes | Yes |
Operating humidity: 0 to 90 %, non-condensing | Yes | Yes | Yes | Yes | Yes |
Storage humidity: 0 to 95 %, non-condensing | Yes | Yes | Yes | Yes | Yes |
|
| ||||
Other Features | |||||
Installation: | 19” 1U | 19” 1U | DIN rail, Wall | Desktop | Desktop |
Casing: | Sheet metal | Sheet metal | Plastic | Sheet metal | Plastic |
Dimensions (L x W x H) in mm: | 440x44x90 | 440x44x90 | L_212.5 H_90.1 D_32.20 | 180x35x80 | 150x29x100 |
Weight: | 1,6 kg | 1,5 kg |
| 0,7 kg | 0,5 kg |
External chassis grounding: M4 thread | Yes | Yes | Yes | Yes | Yes |
| |||||
Web interface | |||||
Web UI access: Any browser | Yes | Yes | Yes | Yes | Yes |
Access tiers: Three-level by login | Yes | Yes | Yes | Yes | Yes |
Dashboard panel: | Yes | Yes | Yes | Yes | Yes |
Overall statistics panel: | Yes | Yes | Yes | Yes | Yes |
System tree panel: sensors and devices displayed in a hierarchy | Yes | Yes | Yes | Yes | Yes |
Dry outputs panel: | Yes | Yes | Yes | No | Yes |
Dry inputs panel: | Yes | Yes | Yes | Yes | Yes |
Event log panel: amount of logs | 300 | 300 | Yes | 300 | 200 |
Logic schemes panel: | Yes | Yes | Yes | Yes | Yes |
Cameras panel: | Yes | Yes | Yes | Yes | Yes |
Map panel: 5 layers | Yes | Yes | Yes | Yes | Yes |
Users panel: | Yes | Yes | Yes | Yes | Yes |
CAN configuration panel: | Yes | Yes | Yes | Yes | Yes |
Graphs panel: | Yes | Yes | Yes | Yes | Yes |
Reset smoke detectors panel: | Yes | Yes | Yes | Yes | Yes |
Preferences panel: Web GUI, Network, Time, Logging, DynDNS, SNMP, RADIUS, FTP backup, VPN Clent, Modbus RTU, GPS, SMTP, Routing | Yes | Yes | Yes | Yes | Yes |
System menu panel: About, Firmware, Export, Support | Yes | Yes | Yes | Yes | Yes |
List of latest sent SMS messages: | 200 | 200 | 200 | 150 | 200 |
Analog sensor power reset: resets smoke sensors | Yes | Yes | Yes | Yes | Yes |
● Built-in □ None ♦ Extension possible ◊ Not extendable