Comparison chart: PDUs
Device description | VT-PDU 4PS | VT-PDU 4MS | ||
---|---|---|---|---|
Description: | Switchable | Switchable | Switchable | Metered per outlet, Switchable |
Device management: Web, SNMP | Yes | Yes | Yes | Yes |
Physical sensors: | CAN, Analog | CAN, Analog | CAN | CAN |
Outlet sensors: e.g current, voltage | - | - | - | Per outlet |
Virtual sensors: e.g. Modbus TCP | Yes | Yes | Yes | Yes |
| ||||
Device description | VT-PDU 4PS | VT-PDU 4MS | ||
Voltage (V): for each outlet | - | - | - | Yes |
Frequency (Hz): for each outlet | - | - | - | Yes |
Current (A): for each outlet | - | - | - | Yes |
Wattage (W): for each outlet (P=I*V) | - | - | - | Yes |
Active/real power (W): for each outlet | - | - | - | Yes |
Active/real energy (Wh): for each outlet | - | - | - | Yes |
Temperature sensor: +/- 1 °C PCB temperature. | Yes | Yes | Yes | Yes |
Power supply voltage sensor 12V DC: Accuracy (1%) | Yes | Yes | Yes | Yes |
| ||||
Interface and supported protocols | VT-PDU 4PS | VT-PDU 4MS | ||
LAN: Ethernet 10/100 Mbit | Yes | Yes | Yes | Yes |
OS: Linux | v.6.2 | v.6.2 | v.6.2 | v.6.2 |
Interface: Any browser | Yes | Yes | Yes | Yes |
Memory RAM: | 128 Mb | 128 Mb | 128 Mb | 128 Mb |
CPU Speed: | 720 MHz | 720 MHz | 720 MHz | 720 MHz |
Total CPU cores: | 2 | 2 | 2 | 2 |
Clock: Built-in clock | Yes | Yes | Yes | Yes |
Timer: Built-in watchdog | Yes | Yes | Yes | Yes |
The maximum amount of sensors: physical sensors, dry contacts, relays | 100 | 100 | 100 | 100 |
The maximum amount of elements: notifications, triggers, timers, logic, sensors, dry contacts, SNMP Get, SNMP Trap, Dial task, and other elements | 700 | 700 | 700 | 700 |
| ||||
Networking / Protocol support | VT-PDU 4PS | VT-PDU 4MS | ||
LTE Gateway mode: Internet access (routing for internal network) (modem ordered separately) | Yes | Yes | No | No |
Network protocols: DHCP; HTTP; HTTPS; SNMP v1, v2c, v3; SMTP; FTP; Syslog; TLS; | Yes | Yes | Yes | Yes |
Modbus TCP / IP | Yes | Yes | Yes | Yes |
Static routing | Yes | Yes | Yes | Yes |
Dynamic DynDNS | Yes | Yes | Yes | Yes |
Access via RADIUS server | Yes | Yes | Yes | Yes |
VPN: secure data communications; secure change of connection between LTE and LAN | Yes | Yes | Yes | Yes |
SSL installation | Yes | Yes | Yes | Yes |
NTP server | Yes | Yes | Yes | Yes |
| ||||
Alerts / Notifications | VT-PDU 4PS | VT-PDU 4MS | ||
Alert types: E-mail, FTP log, Syslog, SMTP, SNMP Traps, SMS (Modem is ordered separately), Web-to-SMS, | Yes | Yes | Yes | Yes |
A maximum number of "mail to" recipients in an E-mail notification: | 20 | 20 | 20 | 20 |
A maximum number of "SMS to" recipients in an SMS notification: also the maximum amount of phone numbers | 20 | 20 | - | - |
| ||||
Virtual sensors | VT-PDU 4PS | VT-PDU 4MS | ||
Ping: Built-in pinging | Yes | Yes | Yes | Yes |
IP cameras: Connect the IP MJPEG camera with a proxy via the master module. Only view, no record. | 4 | 4 | 4 | 4 |
Get SNMP: Read data from external equipment via SNMP PDU GET (v1/2c) | Yes | Yes | Yes | Yes |
Logic schemes: Used to specify automatic actions to events that occur in the system. | Yes | Yes | Yes | Yes |
Timers: Allows you to plan the events in the system. | Yes | Yes | Yes | Yes |
Triggers: Generate events in the system if logic is triggered. | Yes | Yes | Yes | Yes |
SNMP traps | Yes | Yes | Yes | Yes |
Virtual Math element (combine several sensor data and calculate new data) | Yes | Yes | Yes | Yes |
Logic schemes | Yes | Yes | Yes | Yes |
Modbus TCP/IP: read/write | Yes | Yes | Yes | Yes |
| ||||
Power | VT-PDU 4PS | VT-PDU 4MS | ||
Power supply: | 110-240V 50-60 Hz | 110-240V 50-60 Hz | 110-240V 50-60 Hz | 110-240V 50-60 Hz |
Input / Inlet: IEC, 110-240V AC, 50/60Hz | C14 | C20 | C14 | C14 |
Fuse: | 10A, ⌀5x20mm | 16A, ⌀6x30mm | 10A, ⌀5x20mm | 10A, ⌀5x20mm |
Outputs / Outlets: Bistable relays with indication on the front panel. IEC-C13, 110-240V AC, 50/60 Hz. No heat inside! | 4, switched | 8, switched | 4, switched | 4, switched, metered |
Power consumption: | 6W | 6W | 6W | 6W |
Total power load: | 2.4 kW |
|
|
|
Outlet power measurement: | No | No | No | Yes |
Power reservation input terminal: DC 12V backup power, 3.81mm, 2P | Yes | Yes | Yes | Yes |
| ||||
Outputs | VT-PDU 4PS | VT-PDU 4MS | ||
Relays outputs: 12V 0.25A | x2 | x2 | - | - |
Outlet sockets: | x4 IEC 320 C13 | x8 IEC 320 C13 | x4 IEC 320 C13 | x4 IEC 320 C13 |
|
|
|
|
|
Inputs | VT-PDU 4PS | VT-PDU 4MS | ||
Dry contact inputs (contact closures/digital inputs). Extendable using VT440 / Dry contacts extension unit | 2 | 2 | No | No |
Modbus RTU (RS-485): Max. line length 1000m | extension VT485m | extension VT485m | No | No |
OSDP v2 reader extension: | extension VT485r | extension VT485r | No | No |
Inlet socket: | IEC-C14 | IEC-C20 | IEC-C14 | IEC-C14 |
|
|
|
|
|
Other connectors | VT-PDU 4PS | VT-PDU 4MS | ||
Ethernet port: 10/100Mbit | Yes | Yes | Yes | Yes |
USB-C: USB 2.0 HS | Yes | Yes | Yes | Yes |
|
|
|
|
|
External Memory / Logs | VT-PDU 4PS | VT-PDU 4MS | ||
Micro SD card slot (SDXC up to 512 Gb) | Yes | Yes | Yes | Yes |
SD card formatting function (FAT32) | Yes | Yes | Yes | Yes |
USB flash drive: logs, sensor readings, item settings, etc. | Yes | Yes | Yes | Yes |
Send system log to e-mail: Logs, sensor data, elements settings, etc. | Yes | Yes | Yes | Yes |
Sensor dump files: save the per-second samples of analog and discrete sensors | Yes | Yes | Yes | Yes |
Yes | Yes | Yes | Yes | |
Send to FTP server: Logs, sensor data, elements settings, etc. | Yes | Yes | Yes | Yes |
Maximum amount of log files: 10,000 logs/days = 27 years | Yes | Yes | Yes | Yes |
Sample rate/period (logs, graphs) | 1 s | 1 s | 1 s | 1 s |
| ||||
External memory / Logs | VT-PDU 4PS | VT-PDU 4MS | ||
USB flash drive: logs, sensor readings, item settings, etc. | Yes | Yes | Yes | Yes |
Send system log to e-mail: Logs, sensor data, elements settings, etc. | Yes | Yes | Yes | Yes |
Sensor dump files: save the per-second samples of analog and discrete sensors | Yes | Yes | Yes | Yes |
Yes | Yes | Yes | Yes | |
Send to FTP server: Logs, sensor data, elements settings, etc. | Yes | Yes | Yes | Yes |
Maximum amount of log files: 10,000 logs/days = 27 years | Yes | Yes | Yes | Yes |
Sample rate/period (logs, graphs) | 1 s | 1 s | 1 s | 1 s |
| ||||
Modem (extension ordered separately) | VT-PDU 4PS | VT-PDU 4MS | ||
4G LTE modem: ordered separately. | - | - | ||
Modem modes:
| Access / SMS | Access / SMS | - | - |
Modem LED: STATUS | Yes | Yes | - | - |
| ||||
Embedded onboard sensors | VT-PDU 4PS | VT-PDU 4MS | ||
Temperature sensor: +/- 1 °C Case temperature. | Yes | Yes | Yes | Yes |
| ||||
Environmental characteristics | VT-PDU 4PS | VT-PDU 4MS | ||
Operating temperature: 0 to 60 °C | Yes | Yes | Yes | Yes |
Storage temperature: –25 to 85 °C | Yes | Yes | Yes | Yes |
Operating humidity: 0 to 90 %, non-condensing | Yes | Yes | Yes | Yes |
Storage humidity: 0 to 95 %, non-condensing | Yes | Yes | Yes | Yes |
| ||||
Other Features | VT-PDU 4PS | VT-PDU 4MS | ||
Installation: Extension brackets purchased separately | 19” | 19” | Desktop | Desktop |
Dimensions (L x W x H) in mm: | 440*44*80 | 440*44*107 | 219.5*41*107 | 219.5*41*107 |
Weight: | 1,3 kg | 1,5 kg |
|
|
External chassis grounding: M4 thread | Yes | Yes | Yes | Yes |
| ||||
Extensions (Purchased separately) | VT-PDU 4PS | VT-PDU 4MS | ||
VT127 / Vertical brackets: | - | - | Yes | Yes |
VT128 / 19” bracket for one unit: | - | - | Yes | Yes |
VT129 / 19” bracket for two units: | - | - | Yes | Yes |
| ||||
Web interface (panels) | VT-PDU 4PS | VT-PDU 4MS | ||
Dashboard panel: | Yes | Yes | Yes | Yes |
Overall statistics panel: | Yes | Yes | Yes | Yes |
System tree panel: sensors and devices displayed in a hierarchy | Yes | Yes | Yes | Yes |
Dry inputs panel: | Yes | Yes | - | - |
Event log panel: | 200 | 200 | 200 | 200 |
Logic schemes panel: | Yes | Yes | Yes | Yes |
Cameras panel: | Yes | Yes | Yes | Yes |
Map panel: 5 layers | Yes | Yes | Yes | Yes |
Users panel: | Yes | Yes | Yes | Yes |
CAN configuration panel: | Yes | Yes | Yes | Yes |
Graphs panel: | Yes | Yes | Yes | Yes |
Reset smoke detectors panel: | Yes | Yes | Yes | Yes |
Preferences panel: Web GUI, Network, Time, Logging, DynDNS, SNMP, RADIUS, FTP backup, VPN Clent, GPS, SMTP, Routing | Yes | Yes | Yes | Yes |
System menu panel: About, Firmware, Export, Support | Yes | Yes | Yes | Yes |
List of latest sent SMS messages: | 100 | 100 | - | - |
Analog sensor power reset: resets smoke sensors | Yes | Yes | - | - |
Copyright:
Vutlan s.r.o. (LLC)
Remote Infrastructure Monitoring and Control
43 ul.Svornosti, 821 06 Bratislava,
Slovak Republic