VT960, VT960 DC / Corporate monitoring units (legacy)

Front panel of VT960 and VT960 DC:

VT960 back panel:

VT960 DC back panel:

1. "1U 19 inch brackets" - 2x pcs for mounting into a 1U 19" rack slot.

2. "Logo sticker" - Displays the article number of the monitoring unit.

3. "Sticker space" - A place for a sticker, can be used by a user to place an identifier of the system (for example, an IP address)

4. "Modem" - "VT710 / LTE, GPS modem" is ordered separately.

4a. "Modem status" - displays modem status.

4b. "SIM card" - connector with an ejector, used when the modem is installed inside of the appliance.

4c. "GPS active antenna" - Connector, used when the modem is installed inside of the appliance to connect GPS antenna (GPS antenna and antenna output are ordered separately from the modem). (Currently not supported)

4d. "GSM, LTE main antenna" - Connector, used when the modem is installed inside of the appliance to connect GSM or LTE main antenna. (The main antenna is supplied together with the modem).

4e. "LTE auxiliary antenna" - Connector, used when the modem is installed inside of the appliance to connect LTE auxiliary antenna (Auxiliary LTE antenna and antenna output are ordered separately from the modem).

5. "Analog sensors: A1..A8" - 8 RJ12 analog sensor inputs with auto-sensing.

6. "LEDS: E1, E2" - status indicators for x2 12V 0.25A outputs at the back of the unit.

    "LEDS: R1, R2" - status indicators for x2 relays at the back of the unit.

7. "LED: STATUS" - green LED indicates appliance status,

    "LED: CAN»" - green LED indicates CAN bus status.

"CAN" blinks slowly - nothing is connected

"CAN" blinks fast - configuration is in process

"CAN" glows constantly - connected to CAN devices

    "LED: HDD" - green LED indicates 2.5" HDD or SSD status.

    "LED: ERR" - red LED indicates error and traffic.

8. "SD" - MicroSD card connector with ejector, needed to store data.

9. "USB 0" - type miniAB USB-port 2.0, required to connect a USB camera. (Restore of the appliance using USB is temporarily unavailable)

10. "LAN" - Ethernet 10/100 Base-T port, provides an Ethernet connection.

• LEDs - "yellow" (status) and "green" (traffic) show the network traffic. The status LED: flashes green when the system starts up, and shows the connection state (constant green light - the connection is established, blinking green - the connection attempt).

11. "CAN DEVICES" - digital connector RJ12 for the connection of CAN sensors and CAN extensions on a CAN bus, with auto-sensing.

12. "Restart" - restarts the appliance.

      "FEL" - user-defined action button.

      "Shutdown" - softly shuts down the device.

13. "USB 1" - type USB-port 2.0, required to connect a USB camera. (Restore of the appliance using USB is temporarily unavailable)

14. "Extension board: VTX40a " - Ordered separately. Installed inside the unit. Adds: x32 Dry Contact inputs, x8 Isolated Dry Contact Outputs.

15. "" - External chassis grounding, M4 thread.

16. "Power input" - 230V 2A C14 input.

17. "Fuse" - 2A 5*20 mm fuse.

18. "1-WIRE" - For connecting 1-Wire sensors. A serial communication protocol that uses a single data line plus ground reference between the master and 1-Wire slave device.

19. "AV IN" - audio/video input

      "AV OUT" - audio/video output

20. "DC OUTPUT 12V 0.25A Camera PWR" - 12V 0.25A output electronic relay terminal

21. "OUTPUTS 12V 0.25A" - 12V 0.25A output electronic relay terminals

22. "Relays 1, 2" - relay power terminals.

23. "2.5" HDD/SSD bolts" - these bolts hold the SSD/HDD in place inside the monitoring unit.


Developer notes: v2.6, January 2018