VT8110 / Monitoring Unit with PDU (legacy)
VT8110 front and back panel
1. "LAN" - Ethernet 10/100 Base-T port, provides an Ethernet connection.
• LEDs - "yellow" (status) and "green" (traffic) show the network traffic. The status LED: flashes green when the system starts up, and shows the connection state (constant green light - the connection is established, blinking green - the connection attempt).
2. "USB" - type A USB-port 2.0, is required for a USB flash drive to upgrade an appliance.
3. "HS USB" - type miniAB USB-port 2.0, required to connect a USB camera or to restore an appliance.
4. "SMA" - connector, used when the GSM modem is installed inside of the appliance to connect the GSM antenna.
5. "SD" - SD, MicroSD card connector with ejector, needed to store data.
6. "Reset" - resets the appliance.
7. LEDs: "ACT" - indicates appliance status, "CN1" - indicates CAN1 bus traffic, "CN2" - indicates CAN2 bus traffic, "ERR" - indicates error and traffic.
• Blinking "ACT" ............ • Blinking "CN1" ............ • Blinking "CN2"............ • Blinking "ERR»" ..........
8. "CAN" - two equivalent digital connectors RJ12 for the connection of CAN sensors and CAN extensions on a CAN bus, with auto-sensing.
9. "A1..A8" - 8 RJ12 analog sensor inputs with auto-sensing.
10. "Output LEDs" - relays status indicators, "LED * " - Alarm status indicator
11. "Reader" - RJ9 connector for IButton reader or for RFID reader with 1-Wire.
12. "Dry contacts" - empty slot for dry contacts module VT16, used to connect dry contacts on doors, windows, etc.
14. "Sticker" - Place for a sticker that can be written on. For example: you can write an IP address of the master module.
15. "PWR" - Power outputs (AC 100-240 VAC, 50/60HZ).
16. "AC line" - power input 240V 10A. IEC C14 connector (AC 100-240 VAC, 50/60HZ).
17. "Fuse 10A" - type 5*20mm
18. "S/N" - serial number. You will need this serial number if you want to contact our support team. It is important that you do not lose it!
19. "DC 12V" - backup power socket, to connect a battery or a power backup.
20. LED: "ACT" - indicates GSM SIM card status
21. "SIM" - connector with an ejector, used when a GSM modem is installed inside of the appliance to connect the SIM card.
22. "Dip switch" Normal ↑ Off - the system should be always switched to this mode.
Recovery ↓ On - use this option only in case you need to recover manufacturing settings.
developer notes: metal case v.16