SC8100 Remote monitoring system (legacy)
1. "LAN" - Ethernet 10/100 Base-T port, provides an Ethernet connection.
• LEDs - "yellow" (status) and "green" (traffic) show the network traffic. The status LED: flashes green when the system starts up, and shows the connection state (constant green light - the connection is established, blinking green - the connection attempt).
2. "USB" - type A USB-port 2.0, is required for a USB flash drive to upgrade an appliance.
3. "HS" - type miniAB USB-port 2.0, required to connect a USB camera or to restore an appliance.
4. "Reset" - resets the appliance.
5. "SD" - SD card connector with ejector, needed to store data.
6. LEDs: "ACT" - indicates appliance status, "CN1" - indicates CAN1 bus traffic, "CN2" - indicates CAN2 bus traffic, and "ERR»" - indicates error and traffic.
• Blinking "ACT" ............ • Blinking "CN1" ............ • Blinking "CN2"............ • Blinking "ERR»" ..........
7. "CAN" - two equivalent digital connectors RJ12 for the connection of CAN sensors and CAN extensions on a CAN bus, with auto-sensing.
8. "TR" - labeled as "1" on this module. Needed for connection of CAN sensors.
9. "A1..A8" - 8 RJ12 analog sensor inputs with auto-sensing.
10. "SIM" - connector with an ejector, used when a GSM modem is installed inside of the appliance to connect a SIM card.
11. "Outputs 1..4" - 4 relays status indicators.
12. "1-Wire" - RJ9 connector for 1-Wire I-touch I-Button readers with auto-sensing or for Alarm Beakon / Siren connection.
13. "SMA" - connector, used when GSM modem is installed inside of the appliance to connect the GSM antenna.
14. "AC line" - power input 240V. IEC C14 connector.
15. "Fuse" - type 5*20mm
16. "RLY1...RLY4" - 4 relays output connectors. The relays maximum power output - 5A * 240V.
17. "SMA" - optional hole for mounting SMA antenna of GSM modem.
18. "DC 12V" - backup power socket, to connect a battery or a battery backup.
19. "Dry contacts" - empty slot for dry contacts module SC16, used to connect dry contacts on doors, windows, etc.