Monitoring system elements overview
Monitoring system elements overview
The monitoring system may include the following elements:
Analog sensors;
Discrete sensors;
Virtual sensors (elements);
Notifications;
Units;
All the available elements of the system are given in table ctlAllElementsTable
Example. View available system elements:
$ snmptable -Ci -Cb -v2c -cread 192.168.0.193 VUTLAN-SYSTEM-MIB::ctlAllElementsTable
SNMP table: VUTLAN-SYSTEM-MIB::ctlUnitElementsTable
Id Module Num Class Type Name State Value Spec
201001 1 -1 "analog" "temperature" "Temperature" "alarm" "31.5" ""
203001 1 -2 "analog" "voltage" "Voltage" "warning" "11.3" ""
301001 2 -1 "switch" "relay" "Analog Power" "on" "on" ""
102001 3 1 "switch" "outlet" "Relay-1" "off" "off" ""
102002 3 2 "switch" "outlet" "Relay-2" "off" "off" ""
102003 3 3 "switch" "outlet" "Relay-3" "off" "off" ""
102004 3 4 "switch" "outlet" "Relay-4" "off" "off" ""
101001 4 1 "discrete" "dry" "Dry-1" "normal" "on" "reverse=\"1\""
101002 4 2 "discrete" "dry" "Dry-2" "normal" "on" ""
101003 4 3 "discrete" "dry" "Dry-3" "normal" "on" ""
101004 4 4 "discrete" "dry" "Dry-4" "normal" "on" ""
401001 5 1 "devhwr" "reader" "iButton" "not connected" "" ""
301001 5 -1 "switch" "relay" "iButton Power" "on" "on" ""
102001 2 1 "discrete" "door" "Analog-1" "normal" "on" ""
204001 2 2 "analog" "fvoltage" "Analog-2" "low" "0.0" ""
402001 11 1 "devhwr" "usb-cam" "USB Web camera" "unknown" "-" ""
201002 2 3 "analog" "temperature" "Analog-3" "alarm" "28.5" ""
Example. Getting the measured value for the system element with ID=201002:
$ snmpget -v2c -cread 192.168.0.193 VUTLAN-SYSTEM-MIB::ctlUnitElementValue.201002
or without MIB-file
$ snmpget -v2c -cread 192.168.0.193 .1.3.6.1.4.1.39052.1.3.1.7.201002
there 7 - number of table row associated with sensor value, 201002 - sensor ID.
Example. Changing the name of the element with ID=102003:
, multiple selections available,
Related content
Enable SNMP agent parameters / MIB file