End of Life: 31 31.12.2023
Documentation page: https://vutlan.atlassian.net/wiki/spaces/DEN/pages/2313617561/VT608+Switching+PDU+with+8+outlets
Product page: https://vutlan.com/power-distribution-units/153-vt608-switched-ip-pdu.html
...
Function and purpose
The Switched Power Distribution Unit (PDU) is used for load management and allows to switch on/off or reboot up to 8 outlets.
...
Physical Description
Front panel:
...
Back panel:
...
1. "ACT / STATUS" - Green - indicates appliance status
"LEDs: E1, E2" - status indicators for x2 12V 0.25A outputs at the back of the unit.
The LED is ON (orange) - the output is ON (the initial state can be configured).
The LED is OFF (orange) - the output is OFF ((the initial state can be configured).
"LED: CAN" - green LED indicates CAN bus status.
The LED blinks slowly - nothing is connected
The LED blinks fast - configuration is in process
The LED glows constantly - connected to CAN devices
"ERROR» - red - indicates error and traffic.
the operating mode of the device: If everything is normal, the LED is extinguished, if not - there's a constant glow;
software update mode: switches at a rate of 2 times per second;
"OUTLETS 1 - 8" - orange - indicates outlet status.
2. "LAN port" - Ethernet 10/100 Base-T port, provides an Ethernet connection. Read more in this section "LAN, GSM, LTE, RADIUS, DNS, SSL, VPN".
"Orange LED" - orange LED for Ethernet port. It shows network traffic.
"Green LED" - green LED for Ethernet port. It shows network traffic. Flashes green when the system starts up. Shows the connection state (constant green light - the connection is established, blinking green - the connection attempt).
3. This is a slot for "VT760 / LTE modem". Modem is purchased separately!
...
4. "A1..A2" - x2 RJ12 analog sensor inputs with auto-sensing. Read instructions at "Analog sensors connection", "Sensor configuration".
5. "Sticker space" - A place for a sticker, can be used by a user to place an identifier of the system (for example, an IP address).
...
7. "USB" - type miniAB USB-port 2.0. USB ports are needed for USB camera recording, USB Flash for system logs, and system restoration. Read instructions at "Connecting USB camera", "USB camera settings. How to save a video", "Saving system logs on USB flash drive", "USB upgrade or restore of default settings".
8. "RESTART" - the button restarts the appliance. Hold the button for 2 seconds and then let go, the system will restart.
...
11. "FUSE" - Inlet fuse 16A 6x30mm
12. "
" - Chassis grounding, M4 thread. Enhances the immunity of the equipment against conducted and radiated RF disturbances. Please contact a professional electrician before connecting it....
14. "DRY CONTACT INPUTS 1...2" - x2 digital inputs (Type IN). Read instructions at "Connecting dry contacts", "Dry contacts settings".
15. "OUTPUT 12V 0.25A" - 12V 0.25A (for each output) terminals outputs (electronic relay). Read instructions at "Connecting 12V devices to 12V outputs".
16. "CAN" - digital connector RJ12 for the connection of CAN sensors and CAN extensions on a CAN bus, with auto-sensing. Modules can be chained together. Read instructions at "CAN devises connection", "Setting up CAN".
Connection overview diagram
...
Dimensions
...
Inventory
Include Page | ||||
---|---|---|---|---|
|
Technical specifications
Include Page | ||||
---|---|---|---|---|
|
Installing a modem
Please refer to the following articles:
...
Use x3 pcs of supplied screws (M3 6mm) for each bracket to fix it on each side of the enclosure as shown in the picture below. The screws and brackets are supplied with the unit.
...
Device configuration
Frequently asked questions
Question | Answer |
---|---|
Does VT608 monitor the power consumption? | No, this is not supported. |
...