Function and purpose
Relay switchable contact. Can be used together with equipment, for example for switching it ON/OFF. For controlling devices that have dry contact input or controlling their power source. Can manage 5A power for magnetic locks, bolt locks, solenoid electromagnets, sirens, light sources, heaters, air conditioners, etc.
Can be connected to any Vutlan unit with 12V relay outputs.
Technical specifications
Function & purpose | Description |
---|---|
Used for | Can be connected to Vutlan monitoring system with 12V DC outputs. Used as a relay switchable contact. |
Communication | Description |
Input | wire terminal, pitch 3.81mm, 2P |
Outputs | wire terminal, pitch 5.0mm, 2P |
Environmental | Description |
Operating temperature | Temperature: Min. -50 °C - Max.105 °C |
Operating humidity | Humidity : Min. 5% - Max. 95% (Non-Condensing) |
Power | Decription |
Max switching current | 5A |
Max. switching voltage | 250VAC / 30VDC |
Max. switching power | 1250VA / 150W |
Min. contact load | No gold plated: 5VDC 10mA |
Power consumption | 12 mW |
Max. distance m | 200 m |
Mecanical / Packaging | Description |
Dimensions | 60×18×18 mm |
Weight | 60 g |
Mounting | The mounting bracket, sticker, and screws are included. |
General | Description |
Manufactured in | Manufactured in E.U., Slovak republic, Vutlan s.r.o. |
HS Code | 9025 11 800 |
GTIN | 8588009886525 |
Warranty | 90 days |
LED indication
The sensor has a red LED indicator that sticks from the top cover
Normal | Reverse | |
---|---|---|
contact is closed | Red | - |
contact is open | - | Red |
Drawings
Connecting switchable contact
Switchable contact can only be connected to 12V 0.25A outputs of the Vutlan monitoring system. The diagram below explains how to connect two VT11 switchable contacts to the monitoring system.
Usage examples with installation diagram
Example 1. Using "VT11 / dry contact output" to control a device with dry contact input.
Example 2. Control siren, light source, heater.
Example 3. Control magnetic lock, electric motor, solenoid electromagnet
Cable pinouts
Switchable contact uses a standard two-wire cable for connecting to the monitoring unit.
Packaging includes
Supply includes
# | Component | Description | Quantity |
---|---|---|---|
1 | VT11 / Dry Contact Output Switchable contact | 1 pc | |
2 | Two wire cable (2 m) | 1 pc | |
3 | Screw: B3.5, Length 16mm | 1 pcs | |
4 | Terminal plug 5.0 mm, 2P | 1 pc | |
5 | Terminal plug 3.81 mm, 2P | 1 pc | |
6 | Sticker | 1 pc |
Connecting 12V devices to 12V outputs
Introduction
All Vutlan monitoring systems and switched PDUs can connect up to two alarm beacons, for example, a siren and/or strobe, and other low-current devices, for example, a dry contact output module VT11, to E1, E2 - two outputs of electronic relays.
Connection
To connect the alarm beacon to the 12V output, you need to connect the device with a cable to the terminal according to the polarity. By appropriate logic or manually in the device interface, you can turn on or off and/or give a pulse to the siren, strobe, or a signal on a dry contact output. The maximum current consumption is limited by 250 mA.
Check the voltage supply in the test mode. Go to the Main Menu -> System Structure -> Alarm in the system interface. In the window that appears, click "Pulse". The stroboscope lights up, and the siren wails. To configure alarms, you need to configure the logic.
Do not connect the loads to the outputs while the monitoring system is on.
Vutlan accessories for 12V DC outputs
12V DC relay outputs configuration
The page linked: https://vutlan.atlassian.net/wiki/spaces/DEN/pages/601030668
Configuring 12V relays
Page linked https://vutlan.atlassian.net/wiki/spaces/DEN/pages/601030668/12V+0.25A+relay+configuration
Copyright:
Vutlan s.r.o. (LLC)
Remote Infrastructure Monitoring and Control
43 ul.Svornosti, 821 06 Bratislava,
Slovak Republic