Datasheet page: https://vutlan.atlassian.net/l/cp/At2b1ahP
Product page: https://vutlan.com/remote-monitoring-units/180-vt225t-room-monitoring-unit.html
Brochure: https://vutlan.com/index.php?controller=attachment&id_attachment=29
Drivers: https://vutlan.atlassian.net/wiki/spaces/DRIV/pages/2912583997/
Meta tags: Small monitoring unit
, Monitoring unit in a plastic enclosure
, Low-cost monitoring unit
,
Function and purpose
Low-cost remote environmental monitoring unit for small IT rooms. Can monitor temperature, humidity, voltage, leakage, smoke, airflow, and other parameters. It is also used as an I/O controller (e.g. door control, fans, generator, control panels, UPS, circuit breakers, and alarms). Can signal an alarm, activate a siren, send an e-mail notification, or send an SNMP Trap. Can monitor up to 100 physical sensors. Can use up to 700 different elements - notifications, triggers, timers, logic schemes, sensors, and dry contacts. Has a built-in Web interface with virtual sensors, logic schemes, different types of notifications, and control panels. There are built-in servers and agents like HTTP, HTTPS, SNMP v1, 2c, 3, SMTP, Radius, Syslog, FTP, DHCP, and OpenVPN clients.
VT225t is a new model in it’s range. It can be compared to VT335i in a previous range of products.
low cost, affordable
faster processor
memory doubled
plastic case
Physical Description
Front panel:
Back panel:
Side panel:
1. "USB" - micro USB-port 2.0 is needed for USB camera recording, USB Flash for system logs, and system restoration. Read instructions in "Connecting USB camera", "USB camera settings. How to save a video", "Saving system logs on USB flash drive", and "USB upgrade or restore of default settings".
2. "Analog sensors: A1..A4" - x4 RJ12 6P4C analog sensor inputs with auto-sensing. Read instructions at "Analog sensors connection", and "Sensor configuration".
3. "SD card" - MicroSD card slot with an ejector. The card is needed for data storage or the "system restore". Read instructions at "Saving system logs to SD card", and "Restore of the appliance (for VT960 series)".
4. "LEDs: R1, R2" - status indicators for two 12V 0.25A outputs on the front panel.
The LED is ON (orange) - the output is ON (the initial state can be configured).
The LED is OFF (orange) - the output is OFF ((the initial state can be configured).
"LED: ACT" - green LED indicates appliance system status,
- operating mode of the device: switches at a frequency of 2 times per second;
- successful completion of the software update process: switches at a frequency of 4 times per second;
"LED: ALARM" - The LED can be programmed from the interface for alarm indication.
"LED: ERR" - red LED indicates error and traffic.
the operating mode of the device: If everything is normal, the LED is extinguished, if not - there's a constant glow;
software update mode: switches at a rate of 2 times per second;
"LED: CAN" - green LED indicates CAN bus status.
The LED blinks slowly - nothing is connected
The LED blinks fast - configuration is in process
The LED glows constantly - connected to CAN devices
5 "RELAYS 12V 0.25A" - 12V 0.25A (for each output) terminals outputs (electronic relay). Pitch 3.81mm, 3P. Each output has an LED indication "E1, E2". Read the instructions at "Connecting 12V devices to 12V outputs".
6. "Restart" - the button restarts the appliance. Hold the button for 2 seconds and then let go, and the system will restart.
7. "Reset settings" - reset settings to default factory settings. Keep pressing the button for more than 5 seconds. The “ERR” LED will start blinking. This indicates that the factory restoration has started. Wait for 20-60 seconds for the system to restart. The “ACT” LED will start blinking once the system has been restarted. The device can be accessed now.
8. "LAN port" - Ethernet 10/100 Base-T port, provides an Ethernet connection. Read more in this section "LAN, GSM, LTE, RADIUS, DNS, SSL, VPN".
"Orange LED" - orange LED for Ethernet port. It shows network traffic.
"Green LED" - green LED for Ethernet port. It shows network traffic. Flashes green when the system starts up. Shows the connection state (constant green light - the connection is established, blinking green - the connection attempt).
9. "CAN" - digital connector RJ12 6P4C for the connection of CAN sensors/extensions/devices on a CAN bus. Modules can be chained together. Has an LED indicator "CAN". Read the instructions in "CAN devises connection", and "Setting up CAN".
10. "DRY CONTACT INPUTS 1...2" - Digital inputs (Type IN). Pitch 3.5mm, 6P. Read the instructions at "Connecting dry contacts", and "Dry contacts settings".
11. "DC 12V POWER"- 12V DC 2A main power input.
12. "Side switch"
“N: Normal mode” - The switch is switched to the left ←. The switch should be always in this position.
“R: Restore of appliance” - The switch is switched to the right →. Used to load the clean system image from an SD card. Read instructions at “Restore of appliance (for VT335i, VT825i, VT855i, VT960i & VT960ii series and VT855t series)”
Connection overview diagram
Drawing dimensions
Inventory - Package content
Make sure that the contents of the delivery meet the following configuration. Report a missing or damaged component to your supplier. If damage occurred during transportation, contact the appropriate delivery service.
Package content | Description | |
---|---|---|
1 | Monitoring unit VT225t | |
2 | 12V adapter | |
3 | RJ-45 2m patch cable white | |
4 | OTG Micro USB cable adapter | |
5 | x1 - Terminal plug, 3P, 3.5 mm | |
6 | x1 - Terminal plug, 3P, 3.81 mm | |
7 | Self-adhesive rubber foot - 4 pcs | |
8 | Short configuration manual | |
9 | Warranty card |
Technical details
VT335x, VT336x, VT825x, VT855x, VT960x are the monitoring units and can not connect. For scalability please use extension units and embedded boards.
● Built-in □ None ♦ Extension possible ◊ Not extendable
VT960 | ||||||
---|---|---|---|---|---|---|
Device Management: Web, SNMP | Yes | Yes | Yes | Yes | Yes | Yes |
Sensor access: Three-level by login | Yes | Yes | Yes | Yes | Yes | Yes |
Interface | VT960 | |||||
LAN: Ethernet 10/100 Mbit | 2 x 1 Gbit | 100 Mbit | 100 Mbit | 100 Mbit | 100 Mbit | 100 Mbit |
OS: Linux | v.6.2 | v.6.2 | v.6.2 | v.6.2 | v.6.2 | |
Interface: Any browser | Yes | Yes | Yes | Yes | Yes | Yes |
Memory RAM: | 2 Gb | 128 Mb | 128 Mb | 128 Mb | 128 Mb | 128 Mb |
CPU speed: | 1.8 GHz | 1 GHz | 720 MHz | 720 MHz | 720 MHz | 600 MHz |
Total CPU cores: | 8 | 2 | 2 | 2 | 2 | 2 |
Clock: Built-in clock | Yes | Yes | Yes | Yes | Yes | Yes |
Timer: Built-in watchdog | Yes | Yes | Yes | Yes | Yes | Yes |
The maximum amount of sensors: physical sensors, dry contacts, relays | 500 | 150 | 130 | 100 | 100 | 100 |
The maximum amount of elements: notifications, triggers, timers, logic, sensors, dry contacts, SNMP Get, SNMP Trap, Dial task, and other elements | 3000 | 1000 | 1000 | 700 | 700 | 700 |
Networking / Protocol support | VT960 | |||||
LTE Gateway mode: Internet access (routing for internal network) (modem ordered separately) | Yes | Yes | Yes | Yes | Yes | - |
LTE Access mode: Internet access over LTE (modem ordered separately) | Yes | Yes | Yes | Yes | Yes | - |
Network protocols: DHCP; HTTP; HTTPS; SNMP v1, v2c, v3; SMTP; FTP; Syslog; TLS (v1.0, v1.1, v1.2, v1.3) | Yes | Yes | Yes | Yes | Yes | Yes |
Modbus RTU | Using extension VT485m | Using extension VT485m | Using extension VT485m | Using extension VT485m | Using extension VT485m | - |
RS485 / OSDPv2: reader access control | Yes | Using extension VT485R | Using extension VT485R | Using extension VT485R | Using extension VT485R | - |
Modbus TCP / IP | Yes | Yes | Yes | Yes | Yes | Yes |
Static routing | Yes | Yes | Yes | Yes | Yes | Yes |
Dynamic DynDNS | Yes | Yes | Yes | Yes | Yes | Yes |
Access via RADIUS server | Yes | Yes | Yes | Yes | Yes | Yes |
VPN: secure data communications; secure change of connection between LTE and LAN | Yes | Yes | Yes | Yes | Yes | - |
SSL installation | Yes | Yes | Yes | Yes | Yes | Yes |
NTP server | Yes | Yes | Yes | Yes | Yes | Yes |
Alerts / Notifications | VT960 | |||||
Alert types: E-mail, FTP log, Syslog, SMTP, SNMP Traps, SMS (Modem is ordered separately), Web-to-SMS, | Yes | Yes | Yes | Yes | Yes | Yes |
A maximum number of "mail to" recipients in an E-mail notification: | 20 | 20 | 20 | 20 | 20 | 20 |
A maximum number of "SMS to" recipients in an SMS notification: also the maximum amount of phone numbers | 20 | 20 | 20 | 20 | 20 | - |
Virtual sensors | VT960 | |||||
Pings: Built-in function for server pinging. Test the reachability of a host in a network. | Yes | Yes | Yes | Yes | Yes | Yes |
IP cameras: Connect the IP MJPEG camera with a proxy via the master module. Only view, no record. | 4 | 4 | 4 | 4 | 4 | 4 |
Get SNMP: Read data from external equipment via SNMP PDU GET (v1/2c) | Yes | Yes | Yes | Yes | Yes | Yes |
User keys: Add users who have access using an RFID reader. | Yes | Yes | Yes | Yes | Yes | - |
Logic schemes: Used to specify automatic actions to events that occur in the system. | Yes | Yes | Yes | Yes | Yes | Yes |
Timers: Allows you to plan the events in the system. | Yes | Yes | Yes | Yes | Yes | Yes |
Triggers: Generate events in the system if logic is triggered. | Yes | Yes | Yes | Yes | Yes | Yes |
SNMP traps | Yes | Yes | Yes | Yes | Yes | Yes |
Virtual Math element (combine several sensor data and calculate new data) | Yes | Yes | Yes | Yes | Yes | Yes |
Logic schemes | Yes | Yes | Yes | Yes | Yes | Yes |
Modbus TCP/IP: read/write | Yes | Yes | Yes | Yes | Yes | Yes |
Power | VT960 | |||||
Energy efficiency: (EU Energy level) | Grad C | Grad A | Grad A | Grad A | Grad A | Grad A |
Power input (230V AC): | x2 inputs option | x2 inputs option | x2 inputs option | - | - | - |
Power input (24 ÷ 48V DC): | x2 inputs option | x2 inputs option | x2 inputs option | Yes | - | - |
Power input (12V DC): | - | x1 input option | x1 input option | x2 inputs | Input | Input |
Fuse: Fuse at the inlet | 1 A | 1 A | 1 A | PTC | PTC | PTC |
Min. power consumption: | 5 W | 1 W | 1 W | 1 W | 1 W | 1 W |
Max. power consumption: | 25 W | 10 W | 10 W | 10 W | 10 W | 6 W |
The maximum current load on the relay: | 10А | 10А | 10А | 250mА | 250mА | 250mА |
Redundant power supply: built-in voltage monitor, voltage range 9-12.6V. | Yes AC/DC DC/DC | Yes AC/DC DC/DC | Yes AC/DC DC/DC | Yes DC/DC | Yes DC 12V | - |
Outputs | VT960 | |||||
Relay outputs: latching relays 240V*10A | 2 | 2 | 2 | - | - | - |
Relays outputs: 12V 0.25A | 2 | 2 | 2 | 2 | 2 | 2 |
Max. dry contact outputs (contact closures/digital outputs) | 2 | 8 | - | 5 | - | - |
Inputs | VT960 | |||||
Analog port: 6P6C for connection of an analog sensor. (extendable using CAN bus) | 8 built-in ports, extended using extension unit | 8 built-in ports, extended using extension unit | 8 built-in ports, extended using extension unit | 4 built-in ports, extended using extension unit | 4 built-in ports, extended using extension unit | 4 built-in ports, extended using extension unit |
CAN port: Max number of sensors Use CAN-12V-1A for connecting more than 12 devices. | x2 port, x32 devices in total | x2 port, x32 devices in total | x1 port, max. 32 devices | x1 port, max. 32 devices | x1 port, max. 32 devices | x1 port, max. 10 devices |
Dry contact inputs: (contact closures/digital inputs) | 48 | 32 | 16 | 8 | 4 | 2 |
Modbus RTU (RS-485): Max. line length 1000m | Using extension VT485m | Using extension VT485m | Using extension VT485m | Using extension VT485m | Using extension VT485m | - |
OSDP v2 reader extension: | Yes | Using extension VT485R | Using extension VT485R | Using extension VT485R | Using extension VT485R | - |
Video | VT960 | |||||
USB cameras | 1 | 1 | 1 | 1 | 1 | 1 |
IP cameras | x4 | x4 | x4 | x4 | x4 | x4 |
RTSP IP camera | 2 | - | - | - | - | - |
Other connectors | VT960 | |||||
Ethernet port: 10/100Mbit | - | 1 | 1 | 1 | 1 | 1 |
Ethernet port: 10/100/1000Mit | 2 | - | - | - | - | - |
USB 2.0 Type A | 2 | - | - | - | - | - |
USB 2.0 Type C | 1 | 1 | 1 | 1 | 1 | 1 |
Switch Normal / Recovery: returns the device to factory settings | Yes | Yes | Yes | Yes | Yes | Yes |
External Memory / Logs | VT960 | |||||
Micro SD memory card slot (SDXC up to 512 Gb) | Yes | Yes | Yes | Yes | Yes | Yes |
SD card formatting function (FAT32) | Yes | Yes | Yes | Yes | Yes | Yes |
USB flash drive: logs, sensor readings, item settings, etc. | Yes | Yes | Yes | Yes | Yes | Yes |
Send system log to e-mail: Logs, sensor data, elements settings, etc. | Yes | Yes | Yes | Yes | Yes | Yes |
Sensor dump files: save the per-second samples of analog and discrete sensors | Yes | Yes | Yes | Yes | Yes | Yes |
Yes | Yes | Yes | Yes | Yes | Yes | |
Send to FTP server: Logs, sensor data, elements settings, etc. | Yes | Yes | Yes | Yes | Yes | Yes |
Maximum amount of log files: 10,000 logs/days = 27 years | Yes | Yes | Yes | Yes | Yes | Yes |
Sample rate/period (logs, graphs) | 1 s | 1 s | 1 s | 1 s | 1 s | 1 s |
Reservation of settings | VT960 | |||||
“i” series (e.g. VT335i): System settings are compatible | Yes | Yes | Yes | Yes | Yes | |
VT335, VT825, VT855 | No | No | No | No | No | |
Modem (extension ordered separately) | VT960 | |||||
4G LTE modem: ordered separately. | VT7672 | - | ||||
Modem modes:
| Gateway / Access / SMS | Gateway / Access / SMS | Gateway / Access / SMS | Gateway / Access / SMS | Gateway / Access / SMS | - |
Modem LED: STATUS | Yes | Yes | Yes | Yes | Yes | - |
Embedded onboard sensors | VT960 | |||||
Temperature sensor: +/- 1 °C PCB temperature. | Yes | Yes | Yes | Yes | Yes | Yes |
Power supply voltage sensor: Accuracy (1%) | Main & Reserve | Main & Reserve | Main & Reserve | Main & Reserve | Main & Reserve | Yes |
LED indication | VT960 | |||||
Ethernet LAN: LINK | Yes | Yes | Yes | Yes | Yes | Yes |
Ethernet LAN: ACT | Yes | Yes | Yes | Yes | Yes | Yes |
CAN bus: STATUS | Yes | Yes | Yes | Yes | Yes | Yes |
System: STATUS (ACT) | Yes | Yes | Yes | Yes | Yes | Yes |
System: ERROR (ERR) | Yes | Yes | Yes | Yes | Yes | Yes |
System: ALARM | Yes | Yes | Yes | Yes | Yes | Yes |
12V 0.25A outputs: STATUS (e.g. E1, E2) | x2 | x2 | x2 | x2 | x2 | x2 |
MODBUS RTU: STATUS | VT485M | VT485M | VT485M | VT485M | VT485M | - |
ODSP Reader. | Yes | VT485R | VT485R | VT485R | VT485R | - |
NC/NO/COM Relay (e.g. R1, R2) | x2 | x2 | x2 | - | - | - |
Environmental characteristics | VT960 | |||||
Operating temperature: -10 to 70 °C | Yes | Yes | Yes | Yes | Yes | Yes |
Storage temperature: –25 to 85 °C | Yes | Yes | Yes | Yes | Yes | Yes |
Operating humidity: 0 to 90 %, non-condensing | Yes | Yes | Yes | Yes | Yes | Yes |
Storage humidity: 0 to 95 %, non-condensing | Yes | Yes | Yes | Yes | Yes | Yes |
Other Features | VT960 | |||||
Installation: | 19” 1U | 19” 1U | 19” 1U | DIN rail, Wall | Desktop | Desktop |
Casing: | Sheet metal | Sheet metal | Plastic | Sheet metal | Plastic | |
Dimensions (L x W x H) in mm: | 440x44x90 | 440x44x90 | L_212.5 H_90.1 D_32.20 | 180x35x80 | 150x29x100 | |
Weight: | 1,6 kg | 1,5 kg | 0,7 kg | 0,5 kg | ||
External chassis grounding: M4 thread | Yes | Yes | Yes | Yes | Yes | Yes |
Web interface (panels) | VT960 | |||||
Dashboard panel: | Yes | Yes | Yes | Yes | Yes | Yes |
Overall statistics panel: | Yes | Yes | Yes | Yes | Yes | Yes |
System tree panel: sensors and devices displayed in a hierarchy | Yes | Yes | Yes | Yes | Yes | Yes |
Dry outputs panel: | Yes | Yes | Yes | Yes | No | Yes |
Dry inputs panel: | Yes | Yes | Yes | Yes | Yes | Yes |
Event log panel: amount of logs | Yes | 300 | 300 | Yes | 300 | 200 |
Logic schemes panel: | Yes | Yes | Yes | Yes | Yes | Yes |
Cameras panel: | Yes | Yes | Yes | Yes | Yes | Yes |
Map panel: 5 layers | Yes | Yes | Yes | Yes | Yes | Yes |
Users panel: | Yes | Yes | Yes | Yes | Yes | Yes |
CAN configuration panel: | Yes | Yes | Yes | Yes | Yes | Yes |
Graphs panel: | Yes | Yes | Yes | Yes | Yes | Yes |
Reset smoke detectors panel: | Yes | Yes | Yes | Yes | Yes | Yes |
Preferences panel: Web GUI, Network, Time, Logging, DynDNS, SNMP, RADIUS, FTP backup, VPN Clent, Modbus RTU, GPS, SMTP, Routing | Yes | Yes | Yes | Yes | Yes | Yes |
System menu panel: About, Firmware, Export, Support | Yes | Yes | Yes | Yes | Yes | Yes |
List of latest sent SMS messages: | 200 | 200 | 200 | 200 | 150 | 200 |
Analog sensor power reset: resets smoke sensors | Yes | Yes | Yes | Yes | Yes | Yes |
● Built-in □ None ♦ Extension possible ◊ Not extendable
Copyright:
Vutlan s.r.o. (LLC)
Remote Infrastructure Monitoring and Control
43 ul.Svornosti, 821 06 Bratislava,
Slovak Republic