Device description | ||||
---|---|---|---|---|
Description: | Switchable | Switchable | ||
Device management: Web, SNMP | Yes | Yes | ||
Sensor access: Three-level by login | Yes | Yes | ||
Interface and supported protocols | ||||
LAN: Ethernet 10/100 Mbit | Yes | Yes | ||
OS: Linux | v.6.2 | v.6.2 | ||
Interface: Any browser | Yes | Yes | ||
Memory RAM: | 128 Mb | 128 Mb | ||
CPU Speed: | 720 MHz | 720 MHz | ||
Total CPU cores: | 2 | 2 | ||
Clock: Built-in clock | Yes | Yes | ||
Timer: Built-in watchdog | Yes | Yes | ||
The maximum amount of sensors: physical sensors, dry contacts, relays | 100 | 100 | ||
The maximum amount of elements: notifications, triggers, timers, logic, sensors, dry contacts, SNMP Get, SNMP Trap, Dial task, and other elements | 700 | 700 | ||
Networking / Protocol support | ||||
LTE Gateway mode: Internet access (routing for internal network) (modem ordered separately) | Yes | Yes | ||
LTE Access mode: Internet access over LTE (modem ordered separately) | ||||
Network protocols: DHCP; HTTP; HTTPS; SNMP v1, v2c, v3; SMTP; FTP; Syslog; TLS; | Yes | Yes | ||
Modbus RTU (only with USB converter) | Yes, with extension | Yes, with extension | ||
Modbus TCP / IP | Yes | Yes | ||
Static routing | Yes | Yes | ||
Dynamic DynDNS | Yes | Yes | ||
Access via RADIUS server | Yes | Yes | ||
VPN: secure data communications; secure change of connection between LTE and LAN | Yes | Yes | ||
SSL installation | Yes | Yes | ||
NTP server | Yes | Yes | ||
Alerts / Notifications | ||||
Alert types: E-mail, FTP log, Syslog, SMTP, SNMP Traps, SMS (Modem is ordered separately), Web-to-SMS, | Yes | Yes | ||
A maximum number of "mail to" recipients in an E-mail notification: | 20 | 20 | ||
A maximum number of "SMS to" recipients in an SMS notification: also the maximum amount of phone numbers | 20 | 20 | ||
Virtual sensors | ||||
Ping: Built-in pinging | Yes | Yes | ||
IP cameras: Connect the IP MJPEG camera with a proxy via the master module. Only view, no record. | 4 | 4 | ||
Get SNMP: Read data from external equipment via SNMP PDU GET (v1/2c) | Yes | Yes | ||
Logic schemes: Used to specify automatic actions to events that occur in the system. | Yes | Yes | ||
Timers: Allows you to plan the events in the system. | Yes | Yes | ||
Triggers: Generate events in the system if logic is triggered. | Yes | Yes | ||
SNMP traps | Yes | Yes | ||
Virtual Math element (combine several sensor data and calculate new data) | Yes | Yes | ||
Logic schemes | Yes | Yes | ||
Modbus TCP/IP: read/write | Yes | Yes | ||
Power | ||||
Power supply: | 110-240V 50-60 Hz | 110-240V 50-60 Hz | ||
Input / Inlet: 110-240V AC, 50/60Hz | C14, Fuse 10A | C20, Fuse 16A | ||
Fuse: | 10A | 16A | ||
Outputs / Outlets: Bistable relays with indication on the front panel. C13, 110-240V AC, 50/60 Hz. | 4 | 8 | ||
Power consumption: | ||||
Total power load: | 2.4 kW | |||
Power measurement: | No | No | Outputs/Outlets: Bistable relays with indication on the front panel | 4 |
8 Power reservation input terminal: DC 12V backup power, 3.81mm, 2P Used for PCB emergency power reservation. Does not support AC outlets. | Yes | Yes | ||
Outputs | ||||
Relays outputs: 12V 0.25A | x2 | x2 | ||
Sockets: | x4 IEC 320 C13 | x8 IEC 320 C13 | ||
Inputs | ||||
Analog port: 6P6C for connection of an analog sensor. (extendable using CAN bus) | x2 built-in & extadable | x2 built-in & extadable | ||
CAN port: Connect CAN bus sensors and devices Use CAN-12V-1A for connecting more than 12 devices. | x1 port, max. 32 devices | x1 port, max. 32 devices | ||
Dry contact inputs (contact closures/digital inputs) Extadable using CAN bus and Dry contacts unit | x2 built-in & extadable | x2 built-in & extadable | ||
Modbus RTU (RS-485): Max. line length 1000m | Using extension VT485m | Using extension VT485m | ||
OSDP v2 reader extension: | Using extension VT485r | Using extension VT485r | ||
Other connectors | ||||
Ethernet port: 10/100Mbit | Yes | Yes | ||
Micro USB: USB 2.0 HS | Yes | Yes | ||
Switch Normal / Recovery: returns the device to factory settings | □ | Yes | ||
External Memory / Logs | ||||
Micro SD card slot (SDXC up to 512 Gb) | Yes | Yes | ||
SD card formatting function (FAT32) | Yes | Yes | ||
USB flash drive: logs, sensor readings, item settings, etc. | Yes | Yes | ||
Send system log to e-mail: Logs, sensor data, elements settings, etc. | Yes | Yes | ||
Sensor dump files: save the per-second samples of analog and discrete sensors | Yes | Yes | ||
Yes | Yes | |||
Send to FTP server: Logs, sensor data, elements settings, etc. | Yes | Yes | ||
Maximum amount of log files: 10,000 logs/days = 27 years | Yes | Yes | ||
Sample rate/period (logs, graphs) | 1 s | 1 s | ||
External memory / Logs | ||||
USB flash drive: logs, sensor readings, item settings, etc. | Yes | Yes | ||
Send system log to e-mail: Logs, sensor data, elements settings, etc. | Yes | Yes | ||
Sensor dump files: save the per-second samples of analog and discrete sensors | Yes | Yes | ||
Yes | Yes | |||
Send to FTP server: Logs, sensor data, elements settings, etc. | Yes | Yes | ||
Maximum amount of log files: 10,000 logs/days = 27 years | Yes | Yes | ||
Sample rate/period (logs, graphs) | 1 s | 1 s | ||
Modem (extension ordered separately) | ||||
4G LTE modem: ordered separately. | ||||
Modem modes:
| Access / SMS | Access / SMS | ||
Modem LED: STATUS | Yes | Yes | ||
Embedded onboard sensors | ||||
Temperature sensor: +/- 1 °C Case temperature. | Yes | Yes | ||
Environmental characteristics | ||||
Operating temperature: 0 to 60 °C | Yes | Yes | ||
Storage temperature: –25 to 85 °C | Yes | Yes | ||
Operating humidity: 0 to 90 %, non-condensing | Yes | Yes | ||
Storage humidity: 0 to 95 %, non-condensing | Yes | Yes | ||
Other Features | ||||
Installation: | 19” | 19” | ||
Dimensions (L x W x H) in mm: | 440*44*80 | 440*44*80 | ||
Weight: | 1,3 kg | 1,5 kg | ||
External chassis grounding: M4 thread | Yes | Yes | ||
Web interface (panels) | ||||
Dashboard panel: | Yes | Yes | ||
Overall statistics panel: | Yes | Yes | ||
System tree panel: sensors and devices displayed in a hierarchy | Yes | Yes | ||
Dry inputs panel: | Yes | Yes | ||
Event log panel: | 200 | 200 | ||
Logic schemes panel: | Yes | Yes | ||
Cameras panel: | Yes | Yes | ||
Map panel: 5 layers | Yes | Yes | ||
Users panel: | Yes | Yes | ||
CAN configuration panel: | Yes | Yes | ||
Graphs panel: | Yes | Yes | ||
Reset smoke detectors panel: | Yes | Yes | ||
Preferences panel: Web GUI, Network, Time, Logging, DynDNS, SNMP, RADIUS, FTP backup, VPN Clent, GPS, SMTP, Routing | Yes | Yes | ||
System menu panel: About, Firmware, Export, Support | Yes | Yes | ||
List of latest sent SMS messages: | 100 | 100 | ||
Analog sensor power reset: resets smoke sensors | Yes | Yes |
...