Release date: 06 April 2020

End-of-Life Sale date: 01 December 202316 May 2024

End-of-Support date: 01 December 202516 May 2027

Documentation page: https://vutlan.atlassian.net/l/c/gTr18F3Q

...

2. "CAN" - digital connector RJ12 6P4C for the connection of CAN sensors/extensions/devices on a CAN bus. Modules can be chained together. Read the instructions at "CAN devises connection and", and "Setting up CAN".

  • "LED: CAN" - green LED indicates CAN bus status.

  • The LED blinks slowly - nothing is connected

  • The LED blinks fast - configuration is in process

  • The LED glows constantly - connected to CAN devices

...

7. "USB" - micro USB-port 2.0 is needed for USB camera recording, USB Flash for system logs, and system restoration. Read instructions at "Connecting USB camera", "USB camera settings. How to save a video", "Saving system logs on USB flash drive", and "USB upgrade or restore of default settings".

...

9. "OUTPUTS 12V 0.25A" - 12V 0.25A (for each output) terminals outputs (electronic relay). Pitch 3.81mm, 3P. Read instructions at "Connecting 12V devices to 12V outputs".

...

11. "GNSS" - A hole for mounting the GNSS antenna. Antennas are purchased separately from VT335i and separately from VT740. Read more at GPS location, and GPS Service API.

12a. "Restart" - the button restarts the appliance. Hold the button for 2 seconds and then let go, and the system will restart.

...

12c. "Factory reset" - Do not use this button. If you need a factory reset, please use the following optionRestore of appliance (for VT335i, VT825i, VT855i, VT960i & VT960ii series and VT855t series)

13. "Modem slot" - "VT740 / LTE slot modem" can be installed in this slot. This modem is ordered separately. Read instructions at "VT740 / LTE slot modem", and "LAN, GSM, LTE, RADIUS, DNS, SSL, VPN".

14. "DRY CONTACT INPUTS 1...4" - Digital inputs (Type IN). Pitch 3.5mm, 6P. Read instructions at "Connecting dry contacts", and "Dry contacts settings".

15. "DC 12V BACKUP POWER" - 12V DC 2A alternative power input. Pitch 3.81mm, 2P.

...