Documentation page: https://vutlan.atlassian.net/wiki/spaces/DEN/pages/600145921/VT105+Strobe+light

Product page: https://vutlan.com/12v-dc-devices/40-vt105-strobe.html

Function and purpose

12V LED strobe flashlight for warning and alarms. Can be used with monitoring units by connecting it to 12V relay output.

Technical specifications

VT105

Dimensions

⌀73.5mm, Height 45.5mm, cable length 3m

Weight

110g

Input

2-wire cable

Output

LED source

Voltage

12V

Rated current

120mA

Flashing frequency

90/Min

Power consumption

1 Watt

IP rating standard

IP54

Operating temperature

Temperature: Min. -50 °C - Max.105 °C

Operating humidity

Humidity : Min. 5% - Max. 95% (Non-Condensing)

Mounting

Wall or ceiling mounting

HS Code

8531 10 300

Components

Manufactured in E.U.

Special features

LED Security Alarm; Color: red; Material: plastic

Package includes

Package includes:

Package content

Description

Quantity

1

  • x1 Flashing LED device with a cable,

  • x2 back plastic panels

2

Round sticker with holes

1 pc

3

Bolts М3 8mm

2 pcs

4

2.5mm Dowels


2 pcs

5

Screws for dowels, B2.9*20

2 pcs

Connecting a strobe light using only a sticker

A strobe light can be connected to 12V 0.25A outputs of the Vutlan monitoring system. The diagram below explains how to connect "VT105 / Strobe light" to a monitoring system.

Step 1.

Remove the central part of the sticker.

Step 2.

a) Remove the protective paper from one side of the sticker. Apply the sticker to the "VT105 / Stobe light" backside.

b) Remove the protective paper from the second side of the sticker. Stick the Strobe light together with the sticker to the surface. Make sure the cable is laid out neatly using the stickers holes.


Strobe light uses a standard two-wire cable for connecting to the monitoring unit.


Step 3.

Connect the cables to 12V 0.25A outputs of the monitoring unit using a Terminal. The terminal must have a 3.81mm step.

a) Connect the black cable to a "-". Indicated by the "earth" sign.

b) Connect the red cable to a "+". Indicated by the "E1" or "E2" label.

Connecting 12V devices to 12V outputs

Introduction

All Vutlan monitoring systems and switched PDUs can connect up to two alarm beacons, for example, a siren and/or strobe, and other low-current devices, for example, a dry contact output module VT11, to E1, E2 - two outputs of electronic relays.

Connection

To connect the alarm beacon to the 12V output, you need to connect the device with a cable to the terminal according to the polarity. By appropriate logic or manually in the device interface, you can turn on or off and/or give a pulse to the siren, strobe, or a signal on a dry contact output. The maximum current consumption is limited by 250 mA.

Check the voltage supply in the test mode. Go to the Main Menu -> System Structure -> Alarm in the system interface. In the window that appears, click "Pulse". The stroboscope lights up, and the siren wails. To configure alarms, you need to configure the logic.

Do not connect the loads to the outputs while the monitoring system is on.

Vutlan accessories for 12V DC outputs

12V DC relay outputs configuration

The page linked: https://vutlan.atlassian.net/wiki/spaces/DEN/pages/601030668

Connecting a strobe light using dowels

Step 1.

Remove hole parts of the sticker.


Step 2.

Screw the back panel to the backside of the strobe light using 2 M3 screws.


Step 3.

a) Drill two holes for the dowels.

b) Drill a middle hole in the surface if You plan to wire cables through the surface.


Step 4.

a) Insert the dowels into the wall.

b) Insert the adhesive sticker between the wall and the back panel.

c) Screw two M3 screws through the back panel and sticker into the dowels.


Step 5.

Once one back panel is screwed to the wall and the other is screwed to the strobe light, connect both back panels and rotate the strobe light until it is firmly connected.


Step 6.

Connect the wires to the monitoring unit.

12V relay configuration (alarm beacon or strobe light)

12V relay configuration (for example, alarm beacon, strobe light, lock)

a) Login to the web interface of the monitoring system

b) To configure the relay: go to System tree >> Power 12V 0.25A >> Choose relay

c) By default Power-1 and Power-2. Rename it, set the initial state, and set Pulse duration time in seconds to a specific time period.

Connecting 12V devices to 12V outputs

Hardware configuration of 12V devices: Connecting 12V devices to 12V outputs

12V DC Vutlan devices

VT103 / Alarm beacon

VT105 / Strobe light

VT11 / Relay output

Package includes


Copyright:

Vutlan s.r.o. (LLC)

Remote Infrastructure Monitoring and Control

43 ul.Svornosti, 821 06 Bratislava,

Slovak Republic

www.vutlan.com

  • No labels