Function and purpose
VT105 LED strobe light is a 12V DC device for light flashing in case of warnings and alarms.
Connects to 12V DC, 0.25A electronic relay output of Vutlan monitoring systems. Can be configured to sound/light an alarm if an alarm event has been triggered.
Can be used with 3rd party controllers.
Technical specifications
Function and purpose | Description |
---|---|
Used for: | VT105 is a LED Security Alarm powered by 12V relay outputs. |
Flashing frequency: | 90/Min |
Communication | Description |
Input: | 2-wire cable (red/black) |
Output: | LED source |
Environmental | Description |
Operating temperature: | Temperature: Min. -50 °C - Max.105 °C |
Operating humidity: | Humidity : Min. 5% - Max. 95% (Non-Condensing) |
IP rating standard: | IP54 |
Power | Description |
Voltage: | 12V DC |
Rated current: | 120mA |
Power consumption: | 1 Watt |
Mechanical | Description |
Dimensions: | ⌀73.5mm, Height 45.5mm, cable length 3m |
Weight: | 110g |
Mounting: | Wall or ceiling mounting |
Casing: | Color: red and white; Material: plastic |
Genral | Description |
Components: | Manufactured in E.U. |
HS Code: | 8531 10 300 |
GTIN: | 8588009886600 |
Warranty: |
Package includes
Package includes:
Package content | Description | Quantity | |
---|---|---|---|
1 |
| ||
2 | Round sticker with holes | 1 pc | |
3 | Bolts М3 8mm | 2 pcs | |
4 | 2.5mm Dowels | 2 pcs | |
5 | Screws for dowels, B2.9*20 | 2 pcs |
Connecting a strobe light using only a sticker
A strobe light can be connected to 12V 0.25A outputs of the Vutlan monitoring system. The diagram below explains how to connect "VT105 / Strobe light" to a monitoring system.
Step 1.
Remove the central part of the sticker.
Step 2.
a) Remove the protective paper from one side of the sticker. Apply the sticker to the "VT105 / Stobe light" backside.
b) Remove the protective paper from the second side of the sticker. Stick the Strobe light together with the sticker to the surface. Make sure the cable is laid out neatly using the stickers holes.
Strobe light uses a standard two-wire cable for connecting to the monitoring unit.
Step 3.
Connect the cables to 12V 0.25A outputs of the monitoring unit using a Terminal. The terminal must have a 3.81mm step.
a) Connect the black cable to a "-". Indicated by the "earth" sign.
b) Connect the red cable to a "+". Indicated by the "E1" or "E2" label.
Connecting 12V devices to 12V outputs
Page linked https://vutlan.atlassian.net/wiki/spaces/DEN/pages/71181064/Connecting+12V+devices+to+12V+outputs
Connecting a strobe light using dowels
Step 1.
Remove hole parts of the sticker.
Step 2.
Screw the back panel to the backside of the strobe light using 2 M3 screws.
Step 3.
a) Drill two holes for the dowels.
b) Drill a middle hole in the surface if You plan to wire cables through the surface.
Step 4.
a) Insert the dowels into the wall.
b) Insert the adhesive sticker between the wall and the back panel.
c) Screw two M3 screws through the back panel and sticker into the dowels.
Step 5.
Once one back panel is screwed to the wall and the other is screwed to the strobe light, connect both back panels and rotate the strobe light until it is firmly connected.
Step 6.
Connect the wires to the monitoring unit.
12V relay configuration (alarm beacon or strobe light)