Functional description & components

1. "LED: ACTIVITY" - green LED indicates appliance status

"LED: ERROR» - red LED indicates system error and traffic.

2. "Analog sensors: A1..A6" - x6 RJ12 analog sensor inputs with auto-sensing. Read instructions at "Analog sensors connection", "Sensor configuration".

3. "USB" - type miniAB USB-port 2.0, required to connect a USB camera, USB flash, USB hub or to restore an appliance using USB flash.

4. "CAN" - digital connector RJ12 for the connection of CAN sensors and CAN extensions on a CAN bus, with auto-sensing. Read instructions at "CAN devices connection", "Setting up CAN".

5. "LAN port" - Ethernet 10/100 Base-T port, provides an Ethernet connection.

6. "DRY CONTACT INPUTS 1...4" - Digital inputs. Read instructions at "Connecting dry contacts", "Dry contacts settings".

7. "TEMPERATURE SENSOR" - accuracy +/- 1 °C.

8. "MODE" - a DIP switch for changing system modes.

9. "RESTART" - button restarts the appliance. Press the button for several seconds.

10. "OUTPUT 12V 0.25A" - 12V 0.25A output electronic relay terminal. Read instructions at "Connecting 12V devices to 12V outputs".

11. "ISOLATED DRY CONTACTS OUTPUTS 1...4" - Digital outputs 24VDC / 15mA (type OUT). Read instructions at "Connecting dry contacts", "Dry contacts settings".

12. "RS-485 MODBUS RTU" - port for connecting Modbus RTU / RS-485 sensors and devices. Read instructions at "Connecting Modbus RTU sensors to VT336 & VT336PoE", "Configuring Modbus devices".

13. "DC 12V 1A" - DC power input. Instructions are in the section below.

14. "Modem" - "VT770 / LTE, GPS modem" is ordered separately. Read instructions at "Connecting VT770 / LTE modem with GNSS", "Network: LAN, GSM, LTE, RADIUS, DNS, SSL, VPN".

Dimensions

Function & Order options & Technical specifications

Product info is located on the product page "VT336 product page".

Powering the device

:

  1. Power supply with grounding.

  2. Power supply without grounding.

Powering the device using VT-RM-9-12 / Mosfet Redundancy module

VT-RM-9-12 decouples the outputs of the power supplies (9-12VDC, Max. 5A). Automatically supplies load current (Smooth Switchover) from the system input supply with the higher voltage.

Inventory

VT336 package content

Mounting the device on a DIN rail

1
Insert the DIN rail holder as shown in the picture
2
Press the module onto the DIN rail, it should snap.
3

To dismantle the unit from the DIN rail:

  • Use a flat screwdriver and insert it into the DIN rail holder.
  • Pull the handle of the screwdriver to start pulling the DIN rail holder.
  • Now You can pull the enclosure from the DIN rail.

Mounting enclosure guards

1

  • Use pliers or a cutter to cut necessary plastic petals.
  • Use a screwdriver to make necessary holes in the plastic guards.
2
Simply slide it inside the empty spaces until it clicks.
3
Use a screwdriver to pull it out.

Device configuration

  1. Initial Configuration (web interface)
  2. Configuring (web interface)







Developer notes: