Brand / CompanyModbus slave deviceDescriptionParameter

Slave address*

(default)

User defined

Register index

(hexadecimal view)

Function code

Data type

Data orderingPolling period
Circutor

CVM-C10 series

Power analyzer, panelVoltage, V1

0000


Read input register  (0x04)

32 bits unsigned inthigh byte first, high word first10 seconds
Frequency, Hz003C
EastronSDM220 series

Energy meter

Voltage, V1

0000Read input register  (0x04)32 bits IEEE 754 floating point

high byte first, high word first


10 seconds
Active power, Watts000C
Frequency, Hz0046

Slave address* - Usually is set to 1 by the manufacturer. This parameter can be changed manually.