Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 18 Current »

Documentation page: https://vutlan.atlassian.net/wiki/spaces/DEN/pages/583237633/VT11+Relay+output

Product page: https://vutlan.com/digital-output/72-vt11-relay-contact-5a.html

Function and purpose

Relay switchable contact. Can be used together with equipment, for example for switching it ON/OFF. For controlling devices that have dry contact input or controlling their power source. Can manage 5A power for magnetic locks, bolt locks, solenoid electromagnets, sirens, light sources, heaters, air conditioners, etc.

Can be connected to any Vutlan unit with 12V relay outputs.

Technical specifications

VT590

Dimensions

60×18×18 mm

Weight

60 g

Input

wire terminal 3.81mm 2P

Outputs

wire terminal 5.0mm 2P

Operating temperature

Temperature: Min. -50 °C - Max.105 °C

Operating humidity

Humidity : Min. 5% - Max. 95% (Non-Condensing)

Mounting

The mounting bracket, sticker, and screws are included.

Power consumption

12 mW

Max. distance m

200 m

HS Code

9025 11 800

Components

Manufactured in E.U.

Special features

Can be connected to any monitoring system or device with 12V outputs.

Max. switching voltage

250VAC / 30VDC

Max switching current

5A

Max. switching power

1250VA / 150W

Min. contact load

No gold plated: 5VDC 10mA

LED indication

The sensor has a red LED indicator that sticks from the top cover

Normal

Reverse

contact is closed

Red

-

contact is open

-

Red

Drawings

Connecting switchable contact

Switchable contact can only be connected to 12V 0.25A outputs of the Vutlan monitoring system. The diagram below explains how to connect two VT11 switchable contacts to the monitoring system.

Usage examples with installation diagram

Example 1. Using "VT11 / dry contact output" to control a device with dry contact input.


Example 2. Control siren, light source, heater.


Example 3. Control magnetic lock, electric motor, solenoid electromagnet

 

Cable pinouts

Switchable contact uses a standard two-wire cable for connecting to the monitoring unit.

Packaging includes

Supply includes

#

Component

Description

Quantity

1

VT11 / Dry Contact Output

Switchable contact

1 pc

2

Two wire cable (2 m)

1 pc

3

Screw: B3.5, Length 16mm

1 pcs

4

Terminal plug

5.0 mm, 2P

1 pc

5

Terminal plug

3.81 mm, 2P

1 pc

6

Sticker

1 pc

Connecting 12V devices to 12V outputs

All Vutlan monitoring systems and switched PDUs can connect up to two alarm beacons, for example, a siren and/or strobe, and other low-current devices, for example, a dry contact output module VT11, to E1, E2 - two outputs of electronic relays.

Connection

To connect the alarm beacon to the 12V output, you need to connect the device with a cable to the terminal according to the polarity. By appropriate logic or manually in the device interface, you can turn on or off and/or give a pulse to the siren, strobe, or a signal on a dry contact output. The maximum current consumption is limited by 250 mA.

Check the voltage supply in the test mode. Go to the Main Menu -> System Structure -> Alarm in the system interface. In the window that appears, click "Pulse". The stroboscope lights up, and the siren wails. To configure alarms, you need to configure the logic.

Do not connect the loads to the outputs while the monitoring system is on.

Further reading

Configuring 12V relays

12V relay configuration (for example, alarm beacon, strobe light, lock)

a) Login to the web interface of the monitoring system

b) To configure the relay: go to System tree >> Power 12V 0.25A >> Choose relay

c) By default Power-1 and Power-2. Rename it, set the initial state, and set Pulse duration time in seconds to a specific time period.

Connecting 12V devices to 12V outputs

Hardware configuration of 12V devices: Connecting 12V devices to 12V outputs

12V DC Vutlan devices

VT103 / Alarm beacon

VT105 / Strobe light

VT11 / Relay output



Copyright:

Vutlan s.r.o. (LLC)

Remote Infrastructure Monitoring and Control

43 ul.Svornosti, 821 06 Bratislava,

Slovak Republic

www.vutlan.com