Documentation page: https://vutlan.atlassian.net/wiki/spaces/DEN/pages/600145921/VT105+Strobe+light
Product page: https://vutlan.com/12v-dc-devices/40-vt105-strobe.html
Function and purpose
12V LED strobe flashlight for warning and alarms. Can be used with monitoring units by connecting it to 12V relay output.
Technical specifications
VT105 | |
---|---|
Dimensions | ⌀73.5mm, Height 45.5mm, cable length 3m |
Weight | 110g |
Input | 2-wire cable |
Output | LED source |
Voltage | 12V |
Rated current | 120mA |
Flashing frequency | 90/Min |
Power consumption | 1 Watt |
IP rating standard | IP54 |
Operating temperature | Temperature: Min. -50 °C - Max.105 °C |
Operating humidity | Humidity : Min. 5% - Max. 95% (Non-Condensing) |
Mounting | Wall or ceiling mounting |
HS Code | 8531 10 300 |
Components | Manufactured in E.U. |
Special features | LED Security Alarm; Color: red; Material: plastic |
Package includes
Package includes:
Package content | Description | Quantity | |
---|---|---|---|
1 |
| ||
2 | Round sticker with holes | 1 pc | |
3 | Bolts М3 8mm | 2 pcs | |
4 | 2.5mm Dowels | 2 pcs | |
5 | Screws for dowels, B2.9*20 | 2 pcs |
Connecting a strobe light using only a sticker
A strobe light can be connected to 12V 0.25A outputs of the Vutlan monitoring system. The diagram below explains how to connect "VT105 / Strobe light" to a monitoring system.
Step 1.
Remove the central part of the sticker.
Step 2.
a) Remove the protective paper from one side of the sticker. Apply the sticker to the "VT105 / Stobe light" backside.
b) Remove the protective paper from the second side of the sticker. Stick the Strobe light together with the sticker to the surface. Make sure the cable is laid out neatly using the stickers holes.
Strobe light uses a standard two-wire cable for connecting to the monitoring unit.
Step 3.
Connect the cables to 12V 0.25A outputs of the monitoring unit using a Terminal. The terminal must have a 3.81mm step.
a) Connect the black cable to a "-". Indicated by the "earth" sign.
b) Connect the red cable to a "+". Indicated by the "E1" or "E2" label.
Connecting 12V devices to 12V outputs
Introduction
All Vutlan monitoring systems and switched PDUs can connect up to two alarm beacons, for example, a siren and/or strobe, and other low-current devices, for example, a dry contact output module VT11, to E1, E2 - two outputs of electronic relays.
Connection
To connect the alarm beacon to the 12V output, you need to connect the device with a cable to the terminal according to the polarity. By appropriate logic or manually in the device interface, you can turn on or off and/or give a pulse to the siren, strobe, or a signal on a dry contact output. The maximum current consumption is limited by 250 mA.
Check the voltage supply in the test mode. Go to the Main Menu -> System Structure -> Alarm in the system interface. In the window that appears, click "Pulse". The stroboscope lights up, and the siren wails. To configure alarms, you need to configure the logic.
Do not connect the loads to the outputs while the monitoring system is on.
Vutlan accessories for 12V DC outputs
12V DC relay outputs configuration
The page linked: https://vutlan.atlassian.net/wiki/spaces/DEN/pages/601030668
Connecting a strobe light using dowels
Step 1.
Remove hole parts of the sticker.
Step 2.
Screw the back panel to the backside of the strobe light using 2 M3 screws.
Step 3.
a) Drill two holes for the dowels.
b) Drill a middle hole in the surface if You plan to wire cables through the surface.
Step 4.
a) Insert the dowels into the wall.
b) Insert the adhesive sticker between the wall and the back panel.
c) Screw two M3 screws through the back panel and sticker into the dowels.
Step 5.
Once one back panel is screwed to the wall and the other is screwed to the strobe light, connect both back panels and rotate the strobe light until it is firmly connected.
Step 6.
Connect the wires to the monitoring unit.
12V relay configuration (alarm beacon or strobe light)
12V relay configuration (for example, alarm beacon, strobe light, lock)
a) Login to the web interface of the monitoring system
b) To configure the relay: go to System tree >> Power 12V 0.25A >> Choose relay
c) By default Power-1 and Power-2. Rename it, set the initial state, and set Pulse duration time in seconds to a specific time period.
Connecting 12V devices to 12V outputs
Hardware configuration of 12V devices: Connecting 12V devices to 12V outputs
12V DC Vutlan devices
Package includes
Copyright:
Vutlan s.r.o. (LLC)
Remote Infrastructure Monitoring and Control