Documentation page: https://vutlan.atlassian.net/wiki/spaces/DEN/pages/335708171/VT550+Wind+velocity+meter

Product page: https://vutlan.com/analog-sensors/102-vt550-wind-speed-meter.html

...

Function and purpose

At installation on Air conditioners, fans, and other places to measure wind (aiflowairflow) velocity. Sensor controls airflow 0 - 3 m/s. Product page can be found here: "VT550 / Wind velocity meter". The sensor is an analog plug-and-play and it is connected to any analog port of any Vutlan monitoring system.

Safety Instructions

  • Regularly check that the meter is not covered with dust.

Package contents

...

Include Page
VT550 package content
VT550 package content

Connecting optical access sensor

  1. Connect the meter using RJ9 (4p4c) jack to 3 pin JST jack to the sensor.

  2. Connect one end of the RJ11 / RJ12 cable to the monitoring unit into any analog ports (A1...A8) and the other end of RJ11/ RJ12 to the meter.

...

  1. The sensor is

...

  1. plug-and-play and it will appear automatically in a "System tree" of the web

...

  1. interface.

Image Removed

Adjusting sensor sensetivity

Sensor is sold precalibrated. But it is possible to calibrate the meter sensetivity manually if needed. Use flat-head screwdriver to adjust the sensor sensetivity. 

Image Removed

...

Installation inside a rack or cabinet using a bracket

Mounting bracket

Mounting The mounting bracket is supplied with each "VT550 / Wind velocity meter". Use a wire - cutter and the pliers to cut and bend the bracket to Your needs.

...

Installation

...

Info

The sensor measures the speed of the wind. If you install it too far away from the the air-conditioner, there will be no wind velocity or very little.

It is best to install the sensor as close as possible to the origin of the wind. The sensor should work in the stream and the correct installation distance should be obtained by trial and error.

The bracket steel thickness is 0.8 mm. Below You can find how user users can mount the "VT550 /Wind velocity meter" with such a bracket.Image Removed

...

Cable pinouts

"RJ11/RJ12" to "RJ11/RJ12" cable pinouts:Image Removed

...

RJ9 4p4c to 3-pin JST cable pinouts:Image Removed

...

Technical specifications

VT550 / Wind velocity meter

Dimensions

600×18x18 mm

Weight

106 g

Inputs

RJ9 (4p4c)

Outputs

RJ11 / RJ12 (6p4c)

Operating temperature

Min. -10° C, Max.80° C

Operating humidity

Min. 5% - Max. 95% (Non-Condensing)

Mounting

Mounting bracket included for installation inside IT racks and cabinets

Power consumption

60mW

Max. distance from the monitoring unit

50 m

HS Code

9026 80 200

Components

Manufactured in E.U.

Special features

Response time 0.1 sec.

Other

Sensor

The sensor is sold with preconfigured sensitivity.

Drawings

...

View file
nameVT550_velocity_meter.

...

pdf

View file
nameVT550_bracket.pdf

Analog sensor connection

Include Page
Analog sensors connection
Analog sensors connection

Sensor configuration

Include Page
Sensor configuration
Sensor configuration

...

Copyright:

Vutlan s.r.o. (LLC)

Remote Infrastructure Monitoring and Control

43 ul.Svornosti, 821 06 Bratislava,

Slovak Republic

www.vutlan.com