CAN sensors and CAN units connection

  1. Connect CAN devices to any port CAN1 or CAN2 on the monitoring system using a cable supplied. CAN sensors can also be connected to the port of another CAN sensor or CAN unit

...

  1. that is connected

...

  1. to the CAN bus. Determination of the devices and their connection is done through a web

...

  1. interface.

    Info

    You can connect up to a maximum of

...

  1. x12 CAN sensors and CAN devices together on one CAN bus (approximately)

...

  1. !

    If you want to connect more than x12 CAN units, you need to use CAN-12V-1A / CAN Power Supply

Info

You can connect up to x32 CAN units in a CAN bus chain.

  1. The TR should be "ON" for the last sensor on each bus "CAN 1" and "CAN 2". See section "TR" below.

...

Image Removed

...

This procedure applies to the following sensors, which are supported by the appliance and are connected to the CAN ports:

CAN sensors, and modules:

CAN extension unitCAN extensions:

Info

Read more about Setting up CAN sensors.

...


CAN cable and

...

limited line length

The maximum length of the CAN line in Vutlan monitoring systems is 225 m due to limitations on the ohmic resistance of cables with RJ12 connectors.

Info

Vutlan AWG24 cables have low resistance.

Since the conductivity of aluminum is much lower than that of copper, the resistance of CCA cables is much higher than that of pure copper cables of the same size.

It is advisable to use two or three pairs of cables such as UTP Cat3.5.6 with 24AWG with a copper core. It is possible to use a 4-wire or 6-wire TRONIC or UTP CCA cable, but the maximum CAN line length will be reduced.

...

TR termination switch

Note

The last sensor TR switch on a CAN chain must always be terminated, ( switched ON ). Sensors on a CAN bus that is in the middle should have TR switched OFF.

...

Note

Only older Vutlan models have an FR switch.

...

pic.1.1: FR is OFF, TR is ON.                    pic.1.2: FR is OFF, TR is OFF.

Adding CAN modules and sensors

To connect the CAN module or CAN sensor to the CAN bus of the system, go to the interface >> CAN configuration panel >> Select the CAN1 or CAN2 tab (select the connected physical CAN1 or CAN2 port on the master module).

...

The green LED "CAN status" of the device will light up.Image Removed

...

Go to the panel "System Tree" to see the new devices or new sensors. The article numbers for CAN devices are VT4xx. If they do not appear, wait, or refresh.Image Removed

...

Info

If after clicking the "Configure" button the poll is reset to the phrase "Update", then the line is not connected or the terminators on the bus are not agreed. It is necessary to check and change the condition of the TR terminators (See "TR termination switch" section above) on the modules or check and possibly change the connection cables.

Warning

Warning: If the bus is not matched, that is, there are bad contacts or bad cables, or the TR terminator is in the"ON" position on the intermediate devices (position 2 on the VT408), or the line is too short for matching on both CAN end devices, CAN on this line can work malfunctioning, or the line as a whole may not function. (CAN line failure may occur if the parallel CR switch is in state 1, must be in OFF).

LEDs

CAN sensors have LEDs that indicate the following states:

  • Red continuous light, green flickers - no communication with the master module

  • Red continuous light, green is off - there is a connection with the master unit

    ,

    but is not included in the monitoring system (not configured)

  • Red is off, Green continuously light - work as part of a monitoring system

  • All LEDs are off: no power or sensor is defective.

Maximum cable length test

Model

Description

50m

100m

150m

200m

VT408

Sensor extension unit

  


ok



VT408DIN

  

ok

VT430

Rack control unit

  

ok

VT440

Dry contacts unit

  

ok

long-chain

VT460

Smoke, humidity, temperature

  

ok

VT490 / VT490i

Dual humidity and temperature sensor /

Pressure, humidity & temperature sensor

ok

Additional power for long-chain

When connecting a very long chain, you need to use the CAN-12V-1A / CAN Power Supply module for additional power for CAN units/extensions/sensors every 8-12 sensors.

x2 CAN port systems

Some Vutlan main monitoring systems have x2 CAN ports. That means they can support two individual CAN chains. Each chain has to be configured individually. E.g. “VT855t / Data center monitoring unit” has x2 CAN ports.