Connecting analog sensors

Connect the analog sensor by a supplied RJ-11 (6P4C) cable to any analog port "A1 .. A8" or "Sensor" port. The determination of the sensor type and connection will occur automatically.

...

Note

If strong electromagnetic interference is present, we recommend using a 3-pair cable CAN FTP for sensor connection!

6P4C RJ11 cable wiring/pinouts

...

Please refer to the RJ connectors comparison table:

Image Removed

...

Daisy chain connection

Some of the analog sensors can be connected in to a daisy chain. Please refer to the article "Chain connection Connection of analog sensors".

Maximum cable length test

Info

ok = tested

x = failed

Model

50m

100m

120m

150m

200m

VT406

VT407

DC

AC current converter

VT407AC current converter

ok

recommended

  ok




VT410

DC voltage monitor

VT416DC ampere meterVT417AC ampere meter 16A

ok





VT420

Conveter

Converter 4-20mA

ok

recommended

ok




VT500

Temperature sensor

ok

ok




VT501

Outdoor temperature sensor

ok

ok




VT510

Humidity sensor

ok

x




VT530

Access sensor


ok




VT540

Vibration sensor


ok




VT550

Wind velocity meter

ok

x




VT560

Smoke detector


ok




VT570

PIR sensor


ok




VT590

Spot water detector


ok




VT591

Water leak sensor


ok




Extending the number of analog sensors

Using CAN extension "VT408 / Sensor extension unit" it is possible to increase the number of analog sensors connected to the monitoring unit up to 80 sensors.

...

...

Additional articles of interest

Sensor configuration

Adding logic schemes