Function and purpose
Function and purpose
VT604t / Switched PDU with 4 Outlets is a versatile power distribution unit designed for effective load management in various environments. It enables users to switch on, off, or reboot up to eight individual outlets, providing flexible control over connected devices.
...
Connection overview diagram
...
Power Supply Priorities
...
Power supply line | Description |
1 |
This is the main power supply line. The system chooses the power supply input with the biggest Voltage. That is why this power line always has the highest priority. |
2 |
This power line has the second priority and will start working only if there’s a power outage on power line 1. Normally each of these lines supply the system with 11V. Power switching is instant. |
3 |
This power line has the lowest priority because it has the lowest voltage. VT-ACCU or VT-BAT can be connected on this power line. VT-ACCU is charged by the power line 1. The system will start working from VT-ACCU only in case power lines 1 and 2 fail (power outage). VT-BAT battery is not charged. Once it is depleted, the battery has to be manually changed. |
Drawing dimensions
...
19” 1U installation in a rack-cabinet
...
The unit has an “Extension battery slot” at the back of the unit. You can install VT-BAT / Reservation battery 6F22 9V or VT-ACCU / Rechargeable reservation battery.
...
Note |
---|
Warning! If you install VT-ACCU or VT-BAT inside the system with charged batteries and decide to ship it. The system will be operational until the batteries are drained while in transit. |
Package content
Include Page | ||||
---|---|---|---|---|
|
...