Function and purpose
The sensor is needed for the measurement of temperature indoors.
...
The accuracy of the sensor is ± 0.15 °C at room temperature. The maximum The maximum distance from the monitoring unit (or sensor extension unit) is 100 meters.
The maximum amount of sensors and maximum length can be extended using the "VT408 / Sensor extension unit".
Info |
---|
The sensor can not be used on its own. It must be used together with Vutlan monitoring systems. |
Technical specifications
Feature | Description |
---|---|
Type | Analog sensor |
Usage | Temperature measurement |
Product dimensions | (Length, Width, Height) 60×18×18 mm |
Packing weight | 70 g |
Packing size | (Length, Width, Height) 45x45x120 mm |
Cable length | 2m (the custom length of the cable is possible) |
Power Consumption | 60 mW |
Operating temperature | Optimal temperature range: -10° C to +80° C Extended temperature range: -40° С to +100° C |
Operating humidity | 0 to 95 % |
Storage temperature | -40° С to +100° C |
Storage humidity | 0 to 95 % |
Mounting possibilities | Desktop |
...
, Indoor |
...
, Rack-mountable |
...
, Wall mount | |
Max. distance from the unit | 100 m |
Manufactured in (country) | Manufactured in Slovak Republic, E.U. |
HS Code | 9025 11 800 |
Accuracy | ± 0.15 °C at room temperature |
Daisy chain | Not possible |
Inputs terminals | RJ-11 / 6P4C |
Package includes
Include Page | ||||
---|---|---|---|---|
|
Drawings
View file | ||
---|---|---|
|
...
View file | ||
---|---|---|
|
...
Connecting the sensor
The sensor uses a standard Vutlan analog RJS5 RJ11 sensor cable for connecting to the monitoring unit.
...
Analog sensor connection
Include Page | ||||
---|---|---|---|---|
|
Installation using a sticker and a bracket
...
Cut the round bump using a knife so that the bottom of the plastic enclosure will be flat.
...
Option 2.
a) Stick the mounting sensor to the surface using the sticker.
...
b) Stick a sensor to the surface using a screw.
...
Option 3.
Mount the sensor to the surface using a mounting bracket. The mounting bracket and the sensor can be either attached by the stickers or together with screws and nuts.
...
Sensor configuration
Include Page | ||||
---|---|---|---|---|
|
...
Copyright:
Vutlan s.r.o. (LLC)
Remote Infrastructure Monitoring and Control
43 ul.Svornosti, 821 06 Bratislava,
Slovak Republic
www.vutlan.com