Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...

At installation on Air conditioners, fans, and other places to measure wind (aiflowairflow) velocity. Sensor controls airflow 0 - 3 m/s. Product The product page can be found here: "VT550 / Wind velocity meter"

...

  1. Connect the meter using RJ9 (4p4c) jack to 3 pin JST jack to the sensor.
  2. Connect one end of RJ11 / RJ12 cable to the monitoring unit into any analog ports (A1...A8) and the other end of RJ11/ RJ12 to the meter.
  3. Sensor The sensor is a plug-and-play and it will appear automatically in a "System tree" of the web - interface.

Adjusting sensor

...

sensitivity

Sensor The sensor is sold precalibrated. But it is possible to calibrate the meter sensetivity sensitivity manually if needed. Use a flat-head screwdriver to adjust the sensor sensetivitysensitivity

Installation inside a rack or cabinet using a bracket

...

Mounting bracket is supplied with each "VT550 / Wind velocity meter". Use a wire-cutter and the pliers to cut and bend the bracket to Your needs.

...

Bracket steel thickness is 0.8 mm. Below You can find how user users can mount the "VT550 /Wind velocity meter" with such a bracket.

...

VT550 / Wind velocity meter
Dimensions600×18x18 mm
Weight106 g
Inputs

RJ9 (4p4c)

OutputsRJ11 / RJ12 (6p4c)
Operating temperatureMin. -10° C, Max.80° C
Operating humidityMin. 5% - Max. 95% (Non-Condensing)
MountingMounting bracket included for installation inside IT racks and cabinets
Power consumption60mW
Max. distance from the monitoring unit50 m
HS Code9026 80 200
ComponentsManufactured in E.U.
Special featuresResponse time 0.1 sec.