Versions
Net-SNMP ver.5.7.1 or higher is used as an SNMP agent.
Vutlan software ver. 2.0.2 or higher is used as a sub-agent.
Compatibility
Current appliances support SNMP ver. 1, 2с, and 3.
MIB
Details of the monitoring system can be found in a MIB branch .iso.org.dod.internet.private.enterprises.vutlan (OID=.1.3.6.1.4.1.39052).
MIB file may be downloaded at: Any monitoring system → Web Interface → Preferences → SNMP → Download MIB file.
The MIB file has a complex structure, so it is better to use the MIB browser program, instead of SNMP walk.
Currently, the following tables are available :
- ctlUnit - system units:
- ctlUnitModulesTable - system's modules;
- ctlUnitGroupsTable - system's groups;
- ctlUnitElementsTable - elements table;
- ctlUnitLogicsTable - logic schemes;
- ctlUnitTrapNotification - notification SNMP PDU Trap;
- ctlUnitSaveToFlash - saving parameters to flash memory;
- ctlNotifiers - system notifications;
- ctlNotifiersMailersTable - e-mails;
- ctlNotifiersTrapsTable - SNMP Traps;
- ctlNotifiersSMSsTable - SMS;
- ctlVirtualDevices - virtual devices;
- ctlVirtualDevicesTimersTable - timers;
- ctlVirtualDevicesPingsTable - pings;
- ctlVirtualDevicesTriggersTable - triggers;
- ctlVirtualDevicesSnmpgetsTable - SNMP Get virtual sensors;
- ctlHardwareDevices - hardware devices;
- ctlHardwareDevicesCamerasTable - USB and IP cameras;
- ctlInternalSensors - system's sensors;
- ctlInternalSensorsDiscretsTable - discret sensors;
- ctlInternalSensorsAnalogsTable - analog sensors;
- ctlInternalSensorsOutletsTable - outlets and relays;
- ctlCANSensors - CAN bus sensors;
- ctlCANSensorsDiscretsTable - discret sensors;
- ctlCANSensorsAnalogsTable - analog sensors;
- ctlCANSensorsOutletsTable - outlets and relays;
- ctlRsSensors - serial port sensors;
- ctlRsSensorsDiscretsTable - discret sensors;
- ctlRsSensorsAnalogsTable - analog sensors;
- ctlRsSensorsOutletsTable - outlets and relays;