Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 19 Next »

AC. DC metering

Connect AC, and DC transceiver with a supplied RJ-11 (6P4C) or RJ-12 (6P6C) cable to any analog port "A1 .. A8" or "Sensor" port. Determination of the sensor type and connection will occur automatically. Connect transceivers to AC, and DC meters by any 2/4 wire cable.

Change picture

developer notes: change the picture (add change)

This procedure applies to the following AC, and DC devices, which are supported by the appliance and are connected to the analog ports:


AC DC transceivers

Metered

IsolationConnected AC, DC meter
1Current transmitter (VT407)0-5 VHAT-100V1
2DC monitor (VT410)0-75 V1 kV
3Current Loop transceiver (VT420)4-20 mA1 kV4-20mA outputs

For VT410 use only a 3-pair (6P6C) cable for sensor connection!

Connect transceiver to the monitoring unit