The unit has all possibilities for rack control, a PIR sensor for door control, 2 dry contacts, and temperature and humidity sensors.
...
1. "TR" - is the nearest switch to CAN inputs. This switch should be turned "ON" on the last sensor in the CAN chain. The last sensor in the long chain with a length of more than 10 meters, the terminator should be in "OFF" position.
"FR" - the memory switch, is necessary for reprogramming the module (the switch remote from the CAN connectors).
Note |
---|
Do not use the DIP switch "FR", it should always be OFF. If this switch is turned ON, the module will turn off. This switch is only needed for programming purposes! |
...
6. "PIR" - Door IR access sensor. Use a white sticker supplied to control the door open/closed.
...
Technical specifications
Feature | Description |
---|---|
Type / Network interface | CAN digital sensor |
Usage | IR, humidity, and temperature sensor; x2 dry contact inputs (digital inputs); |
Product dimensions | (Width, Height, Depth) 89 x 27.1 x 48.2 mm |
Packing weight | 270 g |
Power supply | Power is supplied over the CAN bus |
Power Consumption | Power Consumption |
Operating temperature | Optimal temperature range: -10° C to +80° C Extended temperature range: -40° С to +100° C |
Mounting possibilities | Desktop Indoor Rack-mountable Wall mount |
Max. distance from the unit | 225 m |
Measured Humidity | 0 ... 95% RH |
Humidity accuracy | 3% |
Measured Temperature | -10 … +85 °С |
Temperature accuracy | 1 °С |
IR sensor distance | minimum 1 cm., maximum 3-4 cm. |
Inputs terminals | Dry contacts / Digital inputs: x2 contacts (pitch 3,5mm, type IN) RJ-12 ports: x2 |
Status Indicators | Red / Green Led |
Manufactured in (country) | Manufactured in Slovak Republic, E.U. |
HS Code | 8471 50 000 |
Daisy chain | Yes, possible using the CAN bus |
Installation
There is a mounting bracket on the unit. Fix unit by M5 or M6 bolts on the cabinet or the rack profile in front of the door. Glue the white sticker on the door in front of the unit IR sensor. Connect CAN input of the unit by RJ11/RJ12 cable supplied to the CAN input of the previous CAN unit or monitoring system. The red LED lights up. Match the TR bus terminators on the attached CAN units. CAN bus terminators TR (position 2 in VT450) should be in the ON state only at the end CAN units port and in Off states (1,2) for all intermediate units. One CAN bus can have not more than 8 CAN units, sensors, and/or another CAN device.
If necessary, connect dry contacts, door sensors, or triggers to the unit.
Connection
To connect the CAN unit to the system, open the interface and go CAN Configuration Select tab CAN.
Click "Configure" and wait. The system starts the CAN bus line survey, and displays the list of connected CAN units and sensors. On the CAN devices, the green LEDs light up.
...