Function and purpose


The sensor/detector is used for leak and level monitoring of conductive liquids in containers, pits, cellars, etc. The sensor has two stainless steel poles. The detector is encapsulated in plastic housing for conductive liquids. Can be placed near plumbing, trays, raised floors, under equipment, sinks, aquariums, sump pumps, refrigerators, dishwashers, toilets, basements, washing machines, water heaters, and garages.

...

SLD / Spot leak detector specifications

Description

The detector is used in combination with the "VT593 / Spot leak sensor" for level monitoring of conductive liquids in containers, pits, cellars, etc. The sensor has two stainless steel poles. The detector is encapsulated in plastic housing for conductive liquids. The sensor can be connected to dry contact inputs (e.g. an alarm system). Can be placed near plumbing, trays, raised floors, under equipment, sinks, aquariums, sump pumps, refrigerators, dishwashers, toilets, basements, washing machines, water heaters, and garages.

Detectable liquids

Clean, polluted & distilled water; acids; alkalis; alcohols, and other electrically conductive liquid

Dimensions

30x20x8 mm

Lengths

1-meter cable

Weight

21 g with cable

Operating humidity

20%RH~100%

Working temperature

-10℃~50℃

Outputs

Two wires, RJ 4P2C plug.

Output form

NO normally open

Special features

The measuring electrodes are resistant to chlorine and salt water (stainless steel AISI 316 / V4A)

Package content

VT593 Water spot detector package content

Installation

Installing the sensor case

Steps

Cut off the ledge at the bottom of the case.

Info

The ledge at the bottom of the case is used for installation inside IT racks.


The sensor can be installed using a screw or a sticker

...