Outlets switching in SC1108 is different from the relay control systems SC8100/8110.

The functionality

...

Each Block module has a panel "Module properties", which has the option to delay the relais - a slider Interval (ms).  Interval determines the delay between relays switching on if several relays should be switched on at the same time.  The minimum delay interval is 22 ms.  Minimum delay interval for simultaneous operation of outlets is 22ms.

Image Modified

In addition,  it is possible to set a default state for all relays.  For this go to panel "Module properties" -> "Outlets Setup".

Individual outlets settings are set in panel "Sensor properties":

Image Modified
Default state - It is possible to set an initial default state for each outlet.  The outlet will switch into this state when the system is started.
Pulse duration - it is possible to set pulse duration for each outlet  . The pulse duration is set in seconds.  Min duration is 1sec.

...

Tab "Outlets" - for switching outlets on/off through system interface

Image Modified

Button "Full off"  is used for emergency shutdown of all outlets. When it is pressed all logics that that were set are disabled.  Attention! The system will issue a warning and ask for the current password!

...

Outlet-3: command is sent ; relay NOT switched ON because of time delay.

Image Modified

To change the state of the relay, tick the appropriate state and click Apply.  Outlets that were not ticked will not change their current status.
Button Set OFF  will set all the relays into OFF state, press button Apply to activate this function.

...