Outlets switching in SC1108 is different from the SC8100/8110.

The functionality

Following options are available for managing outlets:

Settings

Each 8 outlets in the PDU System tree belong to a group of Block N

Each Block module has a panel "Module properties", which has the option to delay the relais - a slider Interval (ms).  Interval determines the delay between relays switching on if several relays should be switched on at the same time.  The minimum delay interval is 22 ms.  Minimum delay interval for simultaneous operation of outlets is 22ms.

In addition,  it is possible to set a default state for all relays.  For this go to panel "Module properties" -> "Outlets Setup".

Individual outlets settings are set in panel "Sensor properties":


Default state - It is possible to set an initial default state for each outlet.  The outlet will switch into this state when the system is started.
Pulse duration - it is possible to set pulse duration for each outlet  . The pulse duration is set in seconds.  Min duration is 1sec.

Attention: Do not forget to save the settings in Flash System Menu -> Save settings to flash

 

Outlets nanagement

Tab "Outlets" - for switching outlets on/off through system interface

Button "Full off"  is used for emergency shutdown of all outlets. When it is pressed all logics that that were set are disabled.  Attention! The system will issue a warning and ask for the current password!

The current state of outlets is displayed with different icon colour.  Grey - switched OFFgreen - switched ON.
The socket icon shows command being sent to change the state of relay.  The line under the socket icon shows command being executed. The figure below shows

Outlet-2 and Outlet- 4: have already been switched to ON state.

Outlet-3: command is sent ; relay NOT switched ON because of time delay.

To change the state of the relay, tick the appropriate state and click Apply.  Outlets that were not ticked will not change their current status.
Button Set OFF  will set all the relays into OFF state, press button Apply to activate this function.

 

Logic

Outlets can be used in the creation of logics; both in executed actions (THEN) and in conditional inputs (IF).
Input conditions (IF) are checked against the actual state of the relay.
PDUs (including SC1108) have more relay states than modules SC8100/SC8110 
A complete list of states: