CAN sensors and CAN units connection

  1. Connect CAN devices to any port CAN1 or CAN2 on the monitoring system using a cable supplied. CAN sensors can also be connected to the port of another CAN sensor or CAN unit that is connected to the CAN bus. Determination of the devices and their connection is done through a web interface.

    Info

    You can connect up to a maximum of x12 CAN sensors and CAN devices together on one CAN bus (approximately)!

    If you want to connect more than x12 CAN units, you need to use CAN-12V-1A / CAN Power Supply

Info

You can connect up to x32 CAN units in a CAN bus chain.

  1. The TR should be "ON" for the last sensor on each bus "CAN 1" and "CAN 2". See section "TR" below.

...

This procedure applies to the following sensors, which are supported by the appliance and are connected to the CAN ports:

...

Info

Read more about Setting up CAN sensors.


CAN cable and limited line length

...

Model

Description

50m

100m

150m

200m

VT408

Sensor extension unit


ok



VT408DIN

ok

VT430

Rack control unit

ok

VT440

Dry contacts unit

ok

long-chain

VT460

Smoke, humidity, temperature

ok

VT490 / VT490i

Dual humidity and temperature sensor /

Pressure, humidity & temperature sensor

ok

Additional power for long-chain

When connecting a very long chain, you need to use the CAN-12V-1A / CAN Power Supply module for an additional power for CAN units/extensions/sensors every 8-12 sensors.

x2 CAN port systems

Some Vutlan main monitoring systems have x2 CAN ports. That means they can support two individual CAN chains. Each chain has to be configured individually. E.g. “VT855t / Data center monitoring unit” has x2 CAN ports.

Additional reading

see also:

Child pages (Children Display)

see also:

Setting up CAN