Function and purpose

A high-performance sensor/detector using microwave radar as a control signal source to detect objects or human movement. This product is an indoor energy-saving high-sensitivity detector.

The scanned signal can penetrate plastic, glass, ceiling, wooden door, and thin walls.

The sensor also has a built-in vibration and humidity sensors.

The maximum amount of sensors connected to the Vutlan monitoring unit and maximum length can be extended using the "VT408 / Sensor extension unit" or “VT408DIN / Extension unitsensor is a CAN bus digital device and can be connected in a chain to any Vutlan monitoring unit.

Microwave radar vs PIR

Why Microwave motion sensor? Quick response time, Higher accuracy than PIR, The scanned signal can penetrate plastic, glass, ceiling, wooden door, and thin walls. This microwave motion sensor reflects the latest development in motion detection technology.

...

9. "Motion window" - The motion sensor movement detection window.

Technical specifications

General parameters

Description

Type:

CAN digital sensor

Usage:

Motion, movement, position, proximity detector/sensor.

Temperature detection.

Vibration detection.

Technology:

Motion: Doppler Principle (transmit and receive signals) using microwave radar with minituarized planar antennas

Daisy chain connection:

Yes, possible with different CAN sensors and modules.

HS Code:

8531 80 950

Manufactured in (country):

Manufactured in Slovak Republic, E.U.

Certification standards:

FCC/CE/SRRC/RoHS

LEDs:

Red when movement detected. Green when no movement detected.

 

RF parameters

Description/value

Frequency Range:

5.725GHz-5.875GHz

Transmit Power:

-4dBm

Antenna:

Built-in flat antennas

 

Temperature sensor

Description/value

Tolerance:

±1 ℃

Hardware parameters

Description/value

Operating Temperature:

Sensor PCB board: from -20 ℃ to +85 ℃

ABS plastic enclosure: from -20 ℃ to +80 °C

PVC RJ cable: from -15 ℃ to +80 °C

Storage temperature:

from -40° С to +100° C

Operating humidity:

Sensor PCB board: 0 to 85%

Storage humidity:

0 to 95 %

Power Consumption:

100 mW

 

 

Installation

 

Installation height:

3 meters is recommended

Detection angle:

120° degrees

Sensing distance:

maximum is 12 meters

Inducting distance:

Radius About 5-6m

Max. Induction Radius:

The radius is 6 meters when hanging height is 3 meters

Cable length:

2 meters

Mounting possibilities:

Wall or ceiling mount

Output terminal:

RJ-11 / 6P4C

Max. distance from the unit:

100 meters from Vutlan controller or from “VT408 / extension unit” or from “VT408DIN / DIN extension unit

Induction range

The graphs below are showing the distance in meters. The darker area in the figures below shows where the sensor’s sensitivity is high, while the light area has low sensitivity.

...