Function and purpose

“VT608t / Switched PDU with 8 outlets” is used for load management and allows to switch on/off or reboot up to 8 outlets.

“VT608t / Switched PDU with 8 outlets” is also used for environmental monitoring (e.g. temperature, humidity, voltage, leakage, smoke, airflow). It is also used as an I/O controller (e.g. door control, fans, generator, control panels, UPS, circuit breakers, and alarms). Can You can use up to 700 different elements - notifications, triggers, timers, logic schemes, sensors, and dry contacts. Has a built-in Web interface with virtual sensors, logic schemes, different types of notifications, and control panels. Has a slot for an LTE modem for an ethernet connection reservation.

...

Supports a full range of Vutlan analog sensors and CAN devices/sensors. Supports Modbus TCP/IP.

...

Virtual sensors include PING, timers, triggers, Logic schemes, SNMP GET, x4 IP cameras, Virtual math elements, and others.

...

Physical Description

Front panel:

...

Back panel:

...

1. "1U 19-inch brackets" - x2 pcs for mounting brackets into a 1U 19" rack slot.

2. "Analog sensors: A1..A8" - 8 RJ12 analog sensor inputs with auto-sensing. Read instructions at "Analog sensors connection", and "Sensor configuration".

3. "LAN port" - Ethernet 10/100 Base-T port, provides an Ethernet connection. Read more in this section "LAN, GSM, LTE, RADIUS, DNS, SSL, VPN".

  • "Orange LED" - orange LED for Ethernet port. It shows network traffic.

  • "Green LED" - green LED for Ethernet port. It shows network traffic. Flashes green when the system starts up. Shows the connection state (constant green light - the connection is established, blinking green - the connection attempt).

4. “USB” - A Micro USB port is needed for USB camera recording, USB Flash for system logs, and system restoration. Read instructions in "Connecting USB camera", "USB camera settings. How to save a video", "Saving system logs on USB flash drive", and "USB upgrade or restore of default settings".

5. "Modem slot" - "VT740 / LTE slot modem" can be installed in this slot. This modem is ordered separately. Read instructions at "VT740 / LTE slot modem", and "LAN, GSM, LTE, RADIUS, DNS, SSL, VPN".

6. "Sticker space" - A place for a sticker, can be used by a user to place an identifier of the system (for example, an IP address).

...

11. "OUTPUTS 12V 0.25A" - 12V 0.25A (for each output) terminals outputs (electronic relay). LED indicators are located on the front panel. Read the instructions at "Connecting 12V devices to 12V outputs".

12. "DRY CONTACT INPUTS 1...2" - Digital inputs (Type IN). Read the instructions at "Connecting dry contacts", and "Dry contacts settings".

13. "CAN 1 / CAN 0" - Two digital connectors RJ12 for the connection of CAN sensors/extensions/devices on a CAN bus. Modules connected to these connectors can be chained together. Read the instructions at "CAN devises connection", and "Setting up CAN".

14. "SD card" - MicroSD card slot with an ejector. The card is needed for data storage or the "system restore". Read instructions at "Saving system logs to SD card", and "Restore of the appliance (for VT960 series)".

...

17. "DC 12V BACKUP POWER" - This is a third backup option. The PCB has three power linespower terminal.

18. "TEMPERATURE SENSOR" - accuracy +/- 1 °C.

...

  • Normal mode: The switch is switched to the left ←. The switch should be always in this position.

  • Restore of appliance: The switch is switched to the right →. Used to load the clean system image from an SD card. Read the instructions at “Restore of appliance”.

Connection overview diagram

...

Drawing dimensions

...

19” 1U installation in a rack-cabinet

1.1

x2 19” brackets should be located in the package together with the system. Use x3 M3 screws to mount the brackets on each side of the unit.

1.2

 

2

 

Use x4 captive nuts and x4 M6 Screws to attached the unit to the rack.

Installing VT485m / RTU modem extension slot

VT855t has a slot for an extension. You can install only one module in this slot. You can install the “VT485m / Modbus RTU modem extension slot” or the “VT485r / OSDPv2 reader extension slot”. Both modules are ordered separately.

Extension

Photo with the module installed

VT485r

VT608t Switched IP Power Distribution Unit PDU with 4 outlets and monitoring (VT485r OSDPv2 reader extension) (back).png

VT485m

VT608t Switched IP Power Distribution Unit PDU with 4 outlets and monitoring (VT485m Modbus RTU extension) (back).png

Installing LTE slot modem

VT855t has a slot for “VT740 / LTE slot modem”. The modem is ordered separately.

Extension

Photo

VT740

VT608t Switched IP Power Distribution Unit PDU with 4 outlets and monitoring (VT740 LTE modem antennas)(front).pngVT608t Switched IP Power Distribution Unit PDU with 4 outlets and monitoring (VT740 LTE modem)(front).png

Package content

Include Page
VT608t package content
VT608t package content

Technical details

See a comparison table with technical details for each Vutlan PDU and monitoring unit at:

Comparison chart: PDUs VT604t & VT608t

Frequently asked questions

Problem

Cause

Solution

Problem

Cause

Solution

The unit is not powering up.

The DIP switch is switched to the “R” position.

Switch the DIP switch to “N” position (Normal).

 

 

 

...