Function and purpose
Needed for light and sound alarms. Has 1.5 m length. Connects to 12V DC, 0.25A electronic relay of Vutlan monitoring systems.
...
Table of Contents | ||
---|---|---|
|
Product page: https://www.vutlan.com/accessories/40-vt105-strobe.html
Documentation link: https://vutlan.atlassian.net/wiki/spaces/DEN/pages/1834680385/VT103+
...
...
Function and purpose
VT103 is needed for light and sound alarms.
Connects to 12V DC, 0.25A electronic relay output of Vutlan monitoring systems. Can be configured to sound/light an alarm if an alarm event has been triggered.
Can be used with 3rd party controllers.
Technical specifications
Function & Purpose | Description |
Device type: | 12V DC sound and light alarm |
Rated voltage: | 12V DC, 1A |
Sound pressure: | 108 dB |
Tone frequency: | 3.8 kHz |
Flash frequency: | 2.5Hz red 150/min |
Output: | Light and sound |
Envrironmental | Description |
Operating temperature: | Min. -50 °C - Max.105 °C |
Operating humidity: | Min. 5% - Max. 95% (Non-Condensing) |
IP rating standard: | IP54 |
Power | Description |
Power consumption: | 250mA |
Mechanical | Description |
Weight: | 150g |
Dimensions: | 70 x 36 x 56 mm |
Mounting: | Wall mount |
Cable length: | 3 meters |
Case color: | ABS plastic, red, white |
General | Description |
Manufactrued in: | Manufactured in E.U. |
HS code: | 8531 10 300 |
GTIN: | 8588009886594 |
Warranty: |
Package includes
Include Page | ||||
---|---|---|---|---|
|
...
Drawings
...
View file | ||
---|---|---|
|
...
...
Installation drawing
View file | ||
---|---|---|
|
...
Connecting 12V devices to Vutlan monitoring systems
Include Page
12V relay configuration (alarm beacon or strobe light)
a) Login to the web interface of the monitoring system
b) To configure the relay: go to System tree >> Power 12V 0.25A >> Choose relay
...
c) By default Power-1 and Power-2. Rename it, set the initial state, and set Pulse duration time in seconds to a specific time period.
...
Additionally: 12V relay configuration
...
Configuration for 12V outputs
Page linked https://vutlan.atlassian.net/wiki/spaces/DEN/pages/601030668/12V+0.25A+relay+configuration
Cable pinouts
Strobe The strobe light uses a standard two-wire cable for connecting to the monitoring unit.
Technical specifications
...
VT105
...
...
...
...
Copyright of:
Vutlan s.r.o. (LLC)
Remote Infrastructure Monitoring and Control
43 ul.Svornosti, 821 06 Bratislava,
Slovak RepublicRepublic