...
...
Function and purpose
“VT825t The VT825t / Remote Monitoring System” System is used designed for comprehensive environmental monitoring (e.g. and I/O control in various industries. Its primary features include:
Environmental Monitoring: Measures critical parameters like temperature, humidity, voltage, leakage, smoke, and airflow. Supports analog, CAN bus, Modbus TCP IP, Modbus RTU (with extension)
...
and other sensors.
I/O Controller: Manages devices such as doors, fans,
...
generators, control panels, UPS systems, circuit breakers, and alarms
...
. You can manage relays, and dry contacts.
Scalability: Supports up to 1000
...
elements
...
, including notifications, triggers, timers, logic schemes, and sensors
...
.
Built-in Web Interface: Provides a user-friendly interface with virtual sensors, logic schemes,
...
notifications, and control
...
Includes x8 analog sensor ports, x1 Ethernet port, x1 Micro USB port, x1 CAN sensor bus port, x2 NC/NO/COM relays, x2 12V DC 0.25A relays, x16 dry contact inputs, x1 SD card slot, power reservation option for AC and DC.
Supports a full range of Vutlan analog sensors and CAN devices/sensors. Supports Modbus TCP/IP.
...
options.
LTE Modem Slot (extension): Ensures connection redundancy with an option for LTE modem integration in case of ethernet failure.
This system is ideal for monitoring and controlling complex environments in data centers, industrial automation, and facility management.
Extensions:
VT740 / LTE slot modem: Ensures connection redundancy with an option for LTE modem integration in case of ethernet failure.
VT485m / Modbus RTU extension or VT485r / OSPDv2 reader extension
Notifications include E-mail, FTP log, Syslog, SMTP, SNMP Traps, Web-to-SMS, and PUSH.
...
Virtual sensors include PING, timers, triggers, Logic schemes, SNMP GET, x4 IP cameras, Virtual math elements, and others.
...
Use cases
The VT825t / Remote Monitoring System offers a versatile solution across a range of applications, making it ideal for:
Data Centers: It monitors temperature, humidity, leakage under raised floors, and airflow to ensure optimal conditions for servers and network equipment. It also controls cooling systems and monitors UPS status, providing alerts in case of power failures or temperature spikes.
Industrial Automation: The VT825t can monitor voltage, leakage, and smoke in factories or manufacturing plants while controlling machinery like fans, circuit breakers, or alarms. It ensures the safety and efficiency of automated processes.
Building Management: It acts as an I/O controller to monitor HVAC systems, smoke detectors, and door control systems in office buildings, ensuring proper functioning and security.
Telecommunication Facilities: Used to manage backup power generators, environmental conditions, and network devices, ensuring continuous uptime for telecommunications infrastructure.
Critical Infrastructure: For facilities like power plants or water treatment plants, it monitors environmental factors and controls equipment to prevent system failures, offering notifications and control via its web interface.
Each of these use cases takes advantage of the VT825t's robust features for environmental monitoring, logic-based control, and notifications, ensuring reliable performance in mission-critical environments.
Order options / Dimensions
...
6. "CAN DEVICES" - digital connector RJ12 for the connection of CAN sensors/extensions/devices on a CAN bus. Modules can be chained together. Read the instructions at "CAN devises connection", and "Setting up CAN".
"LED: CAN" - green LED indicates CAN bus status.
The LED blinks slowly - nothing is connected
The LED blinks fast - configuration is in process
The LED glows constantly - connected to CAN devices
...
Connection overview diagram
...
Power Supply Priorities
...
Power supply line | Description |
---|---|
1, 2, 3 |
These power supply lines are equivalent. The main Vutlan PCB has 3 power lines. If all three power lines are connected and active at the same time, the system chooses the input with the biggest Voltage. Normally each of these lines supply the system with 11V. Power switching is instant. |
4 |
VT-ACCU is charged by the power line 1. The system will start working from VT-ACCU only in case power lines 1,2, and 3 are off (power outage). |
Drawing dimensions
...
19” 1U installation in a rack-cabinet
...
VT825t has a slot for “VT740 / LTE slot modem”. The modem is ordered separately.
Extension | Photo |
---|---|
Installing reservation battery
The unit has an “Extension battery slot” at the back of the unit. You can install VT-BAT / Reservation battery 6F22 9V or VT-ACCU / Rechargeable reservation battery.
...
Note |
---|
Warning! If you install VT-ACCU or VT-BAT inside the system with charged batteries and decide to ship it. The system will be operational until the batteries are drained while in transit. |
Package content VT825t series
...