Product page: https://vutlan.com/analog-sensors/55-vt593-spot-leak-sensor.html

Datasheet page: https://vutlan.atlassian.net/wiki/x/AQAkqQ

Image AddedImage Added

Keywords: #leak #leakage #spot #water #sensor #spot leak sensor #zone #floor #drip #fluid

Function and purpose

The sensor VT593 Spot Leak Sensor detects water by increasing capacitance on measuring an increase in capacitance between two metal poles . The detector is encapsulated in plastic housing. Due on the spot, all housed within a durable plastic casing. Unlike traditional metal-based sensors, it resists corrosion over time thanks to the low applied voltages and the applied leakage detection principle, it does not rust over time.

Product page: https://vutlan.com/analog-sensors/169-vt593-spot-leak-sensor.html

Dimensions

...

Usage example

...

non-corrosive detection method. This design makes it ideal for long-term applications in environments prone to leaks.

The sensor is compatible with any analog port of the Vutlan monitoring unit and is easy to integrate. Its scalability is enhanced by the VT408/Sensor extension unit, allowing you to increase both the number of sensors and the overall length of the sensor network.

Use cases

  1. Data Centers: It can detect water leaks under raised floors on the spot or near critical equipment, preventing costly damage to IT infrastructure.

  2. Industrial Facilities: Helps monitor areas prone to leaks, such as around or under machinery, boilers, heaters, or under piping systems.

  3. Residential and Commercial Spaces: Used to detect leaks in kitchens, bathrooms, boilers, and near appliances such as washing machines, and boilers.

  4. Water Level Meter: The sensor can be used to detect if the water has reached a particular height. For example in a water tray.

This sensor is ideal for long-term monitoring where corrosion could be an issue, and it works seamlessly with Vutlan systems for comprehensive monitoring.

Dimensions

...

Usage example

...

Other installation examples of similar sensors for leak detection can be found in our articles "Water leakage detection using cable sensor and spot sensor" and "Leak detection under raised floors in data centers".

Technical specifications

Image RemovedImage Added
VT593 / Spot leak sensor specifications

Description

The sensor has two RJ connectors. RJ 6P4C connects to the analog port of Vutlan monitoring system. RJ 4P2C connects the leak detector with two poles.

Sensor type:

Analog

Dimensions

60×18×18 mm

Weight

60 g

Input

2 wire (WDC cable)

Detection

CapacitiveSLD / Spot leak detector)

Output

x1 RJ11 / RJ12 (6p4c), 6p4c

Detection

Capacitive

Operating temperature

from -10 °C to +80 °C

Operating humidity

from 5% to 95% (Non-Condensing)

Mounting

Mounting bracket included.

Power consumption

60mW

Max. distance m

100 m

HS Code

9025 80 400

Components

Manufactured in E.U.

Special features

from the monitoring unit or VT408 Analog Sensor Extension Unit

Response time:

15 sec., s

Recovery time:

Depends on how fast the sensor dries out

Image Removed

Manufactured in

Slovak Republic, E.U.

HS Code

9025 80 400

GTIN

8588009886228

Image Added

SLD / Spot leak detector specifications

Description

The detector is used in combination with the "VT593 / Spot leak sensor" for level monitoring of conductive liquids in containers, pits, cellars, etc. The sensor has two stainless steel poles. The detector is encapsulated in plastic housing for conductive liquids. The sensor can be connected to dry contact inputs (e.g. an alarm system). Can be placed near plumbing, trays, raised floors, under equipment, sinks, aquariums, sump pumps, refrigerators, dishwashers, toilets, basements, washing machines, water heaters, and garages.

Detectable liquids

Clean, polluted & distilled water; acids; alkalis; alcohols, and other electrically conductive liquid

Dimensions

30x20x8 30 x 20 x 8 mm

LengthsCable length

1 -meter cablem

Weight

21 g with cable

Operating humidity

20%RH~100%

Working from 20 to 100 % RH

Operating temperature

from -10℃~50℃10℃ to 50℃

Outputs

Two wires, RJ 4P2C plug.

Output form

NO normally open

Special features

The measuring electrodes are resistant to chlorine Chlorine and salt water Salt Water (stainless steel AISI 316 / V4A)

Package content

Linked page VT593 Water spot detector package content

Include Page
VT593 package content
VT593 package content

Installation

Installing the sensor case

Steps

Image RemovedImage Added

Cut off the ledge at the bottom of the case.

Info

The ledge at the bottom of the case is used for installation inside IT racks.


Image RemovedImage Added

The sensor can be installed using a screw or a sticker

Image RemovedImage Added

Installing the detector

Steps

Image RemovedImage Added


The detector can be installed differently depending on the end purpose and the the surface. See below options:

A: For non-conductive surfaces.

B: For conductive surfaces.

C: For liquid level detection.

D: For installing on to vertical surfaces for level detection.

Image RemovedImage Added

The detector can be installed onto a surface using a screw or a sticker.

The detector has a hole in the middle for a screw to fit it.

Image RemovedImage Added

Connecting the sensor

...

Warning

The end poles of the sensor should not touch a conductive surface.

  1. Connect the "VT593 / Spot leak sensor" to the monitoring unit into any available analog port. The connection is plug-an-play. Use RJ11/12 6p4c to RJ11/12 6p4c cable.

  2. Connect the "SLD / Spot leak detector" to the "VT593 / Spot leak sensor".

Analog sensor connection

...

Linked page https://vutlan.atlassian.net/wiki/spaces/DEN/pages/1016274/Analog+sensors+connection

Sensor configuration

Linked page https://vutlan.atlassian.net/wiki/spaces/DEN/pages/1016314/Sensor+configuration

Cable pinouts

  1. The sensor uses a standard Vutlan analog sensor cable (RJ11/RJ12 6P4C to RJ11/RJ12 6P4C) for connecting to the monitoring unit. You can find further instructions in the Analog sensors connectionSensors Connection article

  2. The detector uses two wires. It has a black and red wire. Plus or minus is irrelevant.

Troubleshooting

The following table describes potential problems and their possible causes. It also describes checks you can perform or possible solutions for each. After referring to this table, if you cannot resolve the problem, contact your local Vutlan sales representative for assistance.

Potential Problem

Possible Cause

Possible Solution

The sensor does not appear in the Vutlan monitoring interface

Communication lines are improperly connected.

Check the 6P4C RJ11 communication cable.

The communication cable is inserted into the wrong port.

6P4C RJ11 communication cable must be inserted into the analog port of the Vutlan monitoring system.

Frequently asked questions

Question

Answer

Can I connect “SLD / Spot leak detector” to a 3rd party alarm system without “VT593 / Water spot sensor?

Yes, you can. But it depends on the alarm inputs charachteruistics of a 3rd party device.

Can I connect “WSD / water spot detector” to an dry contact inputs of Vutlan monitoring systems?

No, you can not. The resistance is high and this results in highly unreliable operation.

...