Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...

Table of Contents
stylenone

Product page: https://vutlan.com/analog-sensors/55-vt593-spot-leak-sensor.html

Datasheet page: https://vutlan.atlassian.net/wiki/x/AQAkqQ

Image AddedImage Added

Keywords: #leak #leakage #spot #water #sensor #spot leak sensor #zone #floor #drip #fluid

Function and purpose


The sensor detects water by increasing capacitance on two metal poles. The detector is encapsulated in plastic housing. Due to the low applied voltages and the applied leakage detection principle, it does not rust over time.

Product page: https://vutlan.com/analog-sensors/169-vt593-spot-leak-sensor.html

Dimensions

...

Usage example

...

Can be connected to any analog port (A1...A8) of the Vutlan monitoring unit.

The maximum amount of sensors and maximum length can be extended using the VT408 / Sensor extension unit.

Dimensions

...

Usage example

...

Other installation examples of similar sensors for leak detection can be found in our articles "Water leakage detection using cable sensor and spot sensor" and "Leak detection under raised floors in data centers".

Technical specifications

Image RemovedImage Added
VT593 / Spot leak sensor specifications

Description

The sensor has two RJ connectors. RJ 6P4C connects to the analog port of Vutlan monitoring system. RJ 4P2C connects the leak detector with two poles.

Sensor type:

Analog

Dimensions

60×18×18 mm

Weight

60 g

Input

2 wire (WDC cable)Detection

Capacitive

Output

RJ11 / RJ12 (6p4c)

Detection

Capacitive

Operating temperature

-10 °C to +80 °C

Operating humidity

5% to 95% (Non-Condensing)

Mounting

Mounting bracket included.

Power consumption

60mW

Max. distance m

100 m

HS Code

9025 80 400

Components

Manufactured in E.U.

Special features

Response time:

15 sec., seconds

Recovery time:

Depends on how fast the sensor dries out

Image Removed

Manufactured in

Slovak Republic, E.U.

HS Code

9025 80 400

GTIN

8588009886228

Image Added

SLD / Spot leak detector specifications

Description

The detector is used in combination with the "VT593 / Spot leak sensor" for level monitoring of conductive liquids in containers, pits, cellars, etc. The sensor has two stainless steel poles. The detector is encapsulated in plastic housing for conductive liquids. The sensor can be connected to dry contact inputs (e.g. an alarm system). Can be placed near plumbing, trays, raised floors, under equipment, sinks, aquariums, sump pumps, refrigerators, dishwashers, toilets, basements, washing machines, water heaters, and garages.

Detectable liquids

Clean, polluted & distilled water; acids; alkalis; alcohols, and other electrically conductive liquid

Dimensions

30x20x8 mm

Lengths

1-meter cable

Weight

21 g with cable

Operating humidity

20%RH~100%

Working temperature

-10℃~50℃

Outputs

Two wires, RJ 4P2C plug.

Output form

NO normally open

Special features

The measuring electrodes are resistant to chlorine and salt water (stainless steel AISI 316 / V4A)

Package content

Linked page VT593 Water spot detector package content

Include Page
VT593 package content
VT593 package content

Installation

Installing the sensor case

Steps

Image RemovedImage Added

Cut off the ledge at the bottom of the case.

Info

The ledge at the bottom of the case is used for installation inside IT racks.


Image RemovedImage Added

The sensor can be installed using a screw or a sticker

Image RemovedImage Added

Installing the detector

Steps

Image RemovedImage Added


The detector can be installed differently depending on the end purpose and the the surface. See below options:

A: For non-conductive surfaces.

B: For conductive surfaces.

C: For liquid level detection.

D: For installing on to vertical surfaces for level detection.

Image RemovedImage Added

The detector can be installed onto a surface using a screw or a sticker.

The detector has a hole in the middle for a screw to fit it.

Image RemovedImage Added

Connecting the sensor

...

  1. Connect the "VT593 / Spot leak sensor" to the monitoring unit into any available analog port. The connection is plug-an-play. Use RJ11/12 6p4c to RJ11/12 6p4c cable.

  2. Connect the "SLD / Spot leak detector" to the "VT593 / Spot leak sensor".

Analog sensor connection

...

Linked page https://vutlan.atlassian.net/wiki/spaces/DEN/pages/1016274/Analog+sensors+connection

Sensor configuration

Linked page https://vutlan.atlassian.net/wiki/spaces/DEN/pages/1016314/Sensor+configuration

Cable pinouts

  1. The sensor uses a standard Vutlan analog sensor cable (RJ11/RJ12 6P4C to RJ11/RJ12 6P4C) for connecting to the monitoring unit. You can find further instructions in the Analog sensors connectionSensors Connection article

  2. The detector uses two wires. It has a black and red wire. Plus or minus is irrelevant.

...