Function and purpose

Detects vibration. For installation on walls, windows, etc., sensor controls vibration. For example, detects breaking of window by an intruder if installed on a window glass. Chain connection is possible.

Package includes

Package content can be found at : VT540 package content

Connecting vibration sensor

Sensor uses standard Vutlan analog sensor cable for connecting to the monitoring unit. You can find further instructions at: Analog sensors connection

Sensor can also have a chain connection. Up to 10 sensors in one chain. In this case all sensors in a chain are seen by the system as one sensor.

Installation using a sticker and a bracket

Option 1.

There's a round bump at the bottom of the plastic enclosure of the sensor. It is used for fastening when the sensor is mounted together with the on walls using a screw. In current example it is not needed. If you are planning to mount a device differently, do not follow this step.

Cut the round bump using a knife so that the bottom of plastic enclosure will be flat.

Option 2.

a) Stick the mounting sensor to the surface using the sticker.

or

b) Stick a sensor to the surface using a screw.

Option 3.

Mount the sensor to the surface using a mounting bracket. Mounting bracket and the sensor can be either attached by the stickers or together with screws and nuts.

 

Cable pinouts

Sensor uses standard Vutlan analog sensor cable for connecting to the monitoring unit. You can find further instructions at: Analog sensors connection

Technical specifications

...

VT590

...

RJ-12 / RJ-11 (6p4c)

...

Table of Contents
stylenone

Documentation page: https://vutlan.atlassian.net/wiki/spaces/DEN/pages/583237633/VT11+Relay+output

Product page: https://vutlan.com/digital-output/72-vt11-relay-contact-5a.html

...

Function and purpose

The VT11 Dry Contact Output is a versatile relay output (relay switchable contact) designed for controlling various devices and systems. It offers both relay output and dry contact output capabilities, allowing it to function effectively in multiple applications.

The VT11 is ideal for security systems, HVAC control, and other automation tasks where reliable switching of devices is essential. Its ability to act as both a relay and a dry contact output enhances its usability across different setups.

Can manage 5A power for magnetic locks, bolt locks, solenoid electromagnets, sirens, light sources, heaters, air conditioners, etc.

Can be connected to any Vutlan unit with 12V relay outputs and managed through a Vutlan Web UI.

Use cases

These applications demonstrate the versatility of the VT11 in various settings, from security and automation to HVAC and industrial uses.

  1. Access Control Systems: The VT11 can be used to control magnetic locks or electronic strikes, providing secure access to restricted areas. It can trigger the locking mechanism based on input from access control systems.

  2. Alarm Systems: In security applications, the VT11 can activate sirens or notification lights when an alarm is triggered, ensuring prompt alerts in case of unauthorized access or emergencies.

  3. HVAC Control: The VT11 can manage heating and cooling units by switching them ON or OFF based on predefined conditions, improving energy efficiency and maintaining desired indoor climate.

  4. Lighting Control: It can control lighting systems, allowing for automated ON/OFF functions based on occupancy sensors or timers, enhancing energy savings.

  5. Industrial Automation: The VT11 can be integrated into manufacturing processes to control machinery or equipment, allowing operators to manage power sources effectively and automate workflows.

  6. Remote Monitoring: When used with a monitoring system, the VT11 can provide remote control capabilities, enabling users to manage devices and receive status updates from anywhere.

Technical specifications

Function & purpose

Description

Used for

5A relay switchable contactor or Dry contact output

Communication

Description

Input

wire terminal, pitch 3.81mm, 2P

Outputs

wire terminal, pitch 5.0mm, 2P

Environmental

Description

Operating temperature

Temperature: Min. -

10

50 °C - Max.

80

105 °C

Operating humidity

Humidity : Min. 5% - Max. 95% (Non-Condensing)

Power

Decription

Max switching current

5A

Max. switching voltage

MountingMounting

250VAC / 30VDC

Max. switching power

1250VA / 150W

Min. contact load

No gold plated: 5VDC 10mA

Power consumption

12 mW

Max. distance m

200 m

Mecanical / Packaging

Description

Dimensions

60×18×18 mm

Weight

60 g

Mounting

The mounting bracket, sticker, and screws are included

. Installed on the surface where possible vibration is possible. E.g. windows, doors and etc.Power consumption60mWMax. distance m150 mHS Code9025 11 800ComponentsManufactured in E.U.Special featuresDaisy chain connectable. Analog sensor.

...

.

General

Description

Manufactured in

Manufactured in E.U., Slovak republic, Vutlan s.r.o.

HS Code

9025 11 800

GTIN

8588009886525

Warranty

90 days

LED indication

The sensor has a red LED indicator that sticks from the top cover

Normal

Reverse

contact is closed

Red

-

contact is open

-

Red

Drawings

...

Connecting switchable contact

Switchable contact can only be connected to 12V 0.25A outputs of the Vutlan monitoring system. The diagram below explains how to connect two VT11 switchable contacts to the monitoring system.

...

Usage examples with installation diagram

Example 1. Using "VT11 / dry contact output" to control a device with dry contact input.

...


Example 2. Control siren, light source, heater.

...


Example 3. Control magnetic lock, electric motor, solenoid electromagnet
Image Added

 

Cable pinouts

Switchable contact uses a standard two-wire cable for connecting to the monitoring unit.

...

Packaging includes

Include Page
VT11 package content
VT11 package content

Connecting 12V devices to 12V outputs

Page linked https://vutlan.atlassian.net/wiki/spaces/DEN/pages/71181064/Connecting+12V+devices+to+12V+outputs

Configuring 12V relays

Page linked https://vutlan.atlassian.net/wiki/spaces/DEN/pages/601030668/12V+0.25A+relay+configuration

API: Switching devices

Page linked https://vutlan.atlassian.net/wiki/spaces/API/pages/335904815/Switching+devices

...

Copyright:

Vutlan s.r.o. (LLC)

Remote Infrastructure Monitoring and Control

43 ul.Svornosti, 821 06 Bratislava,

Slovak Republic

www.vutlan.com