Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...

Info

Read more about Setting up CAN sensors.

...


CAN cable and limited line length

The maximum length of the CAN line in Vutlan monitoring systems is 225 m due to limitations on the ohmic resistance of cables with RJ12 connectors.

Info

Vutlan AWG24 cables have low resistance.

Since the conductivity of aluminum is much lower than that of copper, the resistance of CCA cables is much higher than that of pure copper cables of the same size.

It is advisable to use two or three pairs of cables such as UTP Cat3.5.6 with 24AWG with a copper core. It is possible to use a 4-wire or 6-wire TRONIC or UTP CCA cable, but the maximum CAN line length will be reduced.

...