Function and purpose

...

You can use a range of Sensors/Meters/Devices for Modbus.

Testing VT485m PCB using two Vutlan controllers

This section is useful for installers.

You can test the VT485m PCB using x2 Vutlan monitoring units.

  1. Install VT485m on Vutlan monitoring system A and Vutlan monitoring system B.

  2. Connect B- to B-. Connect A+ to A+.

Note

Do not connect the GND!!!

...

 

VT485m

Cables

VT485m

image-20240206-140600.pngImage Added

 

B-

red

B-

A+

blue

A+

  1. Activate Modbus RTU settings on both systems. You can leave all settings by default on both systems. Web UI >> Preferences panel >> Modbus RTU tab >> Enable Modbus RTU

...

  1. Web UI >> System tree panel >> Add element “+” sign >> Modbus RTU (reading) >> Leave all settings by default >> Additional tab >> Test button

The VT485m which is the master will blink with a blue LED.

The VT485m which is the slave will blink with a red LED.

Test complete!

Info

It is ok, if “Modbus value, “Modbus raw answer” values give errors, because the PCB are not meters. They do not have the values by themselves.

...

...